Revised 1/3/01 • UNI/59

7

© 2001 Automated Logic Corporation

page; refer to the 

U5I Module Driver

 document 

for details.

Setting the flow sensor’s zero point 
(T-Line modules)

1. Turn off the Air Handling Unit serving the 

VAV box you are calibrating.

2. In SuperVision, view the UNI module 

driver Status page (FB#15).

3. On the Flow Calibration table, subtract the 

FB's Current Value from the 0.00 Value. 
For example, if the Current Value is 128 
and the 0.00 Value is 130, the result is 2 
(130 - 128 = 2).

4. On the module driver's Parameter page, 

enter this result in the Flow Zero Offset 
parameter.

5. Check the module driver's Status page 

again. If the Adjusted Value on the 
Calibration table matches the 0.00 Value, 
calibration is complete. If not, repeat steps 
3 through 5.

Troubleshooting

If there is a problem and you are not receiving 
correct values from the equipment, use the 
Diag Port to troubleshoot the problem (see 
Figure 2 on page 3). 

1. On the module driver Parameter page, in 

the Diagnostic Port Setup section, enter 
the connection information you will be 
using.

2. Connect a DC95 or DC99 cable between 

the Diag Port and a computer that is 
running a communications program like 
HyperTerminal or Terminal. To make your 
own cable, use the diagrams in Figure 8.

3. Set up your communications program 

with the correct COM port and baud rate 
settings to display the diagnostic 
information output by the UNI/59. The 
diagnostic messages have been written to 

help you understand what is happening; 
see Figure 9 on page 8.

4. Refer to “Troubleshooting Tips” for 

possible solutions. If you are unable to 
solve the problem, save the diagnostic 
capture to a file and contact Technical 
Support at (770) 429-3002.

Understanding the Diagnostic 
Capture

Different levels of detail are provided by the 
five diagnostic levels. Level 4 contains the 
most detail and is shown in the example in 
Figure 9 on page 8. The diagnostic level is 
determined by the 

Diagnostic Port Setup

 

section on the Parameter page.

Troubleshooting Tips

If you are having trouble communicating with 
the UNI/59, check these items before 
contacting Technical Support.

• Make sure the serial cable is connected 

at both ends. In more complex systems, 
make sure that all cables involved are 
attached correctly.

• Make sure the UNI/59 and the T-Line or 

U-Line modules have power and are 
turned on. In more complex systems, 
make sure all equipment has power and 
is turned on. Some devices, especially 
communication devices, receive power 
from a source other than a power cable 
or adapter (for example, some devices 
receive power through communication 

 Figure 8. Diag Port wiring diagrams

  & '" (
)* ' +(
,* ' -(
. ' !(

#  '" (

,* ' -(
)* ' +(

. ' !(

  & '" (
)* ' +(
,* ' -(
. ' !(

#  '-! (

,* ' +(

)* ' -(

. ' /(

Содержание UNI/59

Страница 1: ...r brand and product names are trademarked by their respective companies Technical Instructions UNI 59 Using the UNI 59 2 Specifications 2 Mounting 3 Power Wiring 3 Communicating with the UNI 59 3 Conn...

Страница 2: ...document at http www automatedlogic com or the SupportPlus CD for more information Make sure you use the correct module driver for your application CAUTION Changes or modifications to this unit not ex...

Страница 3: ...100VA maximum Take appropriate isolation measures when mounting the UNI 59 module in a control panel where non Class 2 devices 120VAC or greater or wiring are present You can power several modules fr...

Страница 4: ...modules The UNI 59 supports up to 59 T Line or U Line modules If you are using T Line modules you must use a REPOPT repeater after every 20 modules on the Unet If you are using U Line modules you must...

Страница 5: ...To set the baud rate at 156 kbps when using an ARC156 CMnet set the baud rate jumper to Arc156 see Figure 5 To set the baud rate at 38 4 kbps set the baud rate jumper to 9600 38 4K and set the first...

Страница 6: ...e UNI 59 s module driver and look at the module status report in SuperVision to make sure the module type and number agree with the module The module type for the UNI 59 is 76 To view the module statu...

Страница 7: ...ur own cable use the diagrams in Figure 8 3 Set up your communications program with the correct COM port and baud rate settings to display the diagnostic information output by the UNI 59 The diagnosti...

Страница 8: ...tch s position turn the UNI 59 module off first Once you have adjusted the switch turn the module back on 1 Connect the computer s serial port to the EIA 232 port of the APT using a standard straight...

Страница 9: ...ains the Run and Error LED signals in detail to assist troubleshooting Power indicates power is being supplied to the module CMnet Tx lights when the module transmits data over the CMnet CMnet Rx ligh...

Страница 10: ...ticker on the back of the module also shows the date the module was manufactured The first three characters on the sticker indicate the type of module The next two characters show the year and month o...

Отзывы: