Revised 1/3/01 • UNI/59

4

© 2001 Automated Logic Corporation

up before the proper voltage is verified.

2. Make sure the 24VAC power source is off.

3. Connect the power wires to the module’s 

power terminals labeled Ground and 
24VAC.

4. Apply power to the transformer.

5. Make sure that 24VAC is present at the 

module’s power input terminals.

6. Set the module’s address. Refer to 

“Addressing” on page 5 for details about 
setting the address.

7. Turn the module’s power switch on.

When the module turns on, the Power, 
Run and Error LEDs turn on and the Run 
and Error LEDs begin blinking. The Error 
LED then turns off. (See “LEDs” on page 
for more information about LED signals.) 

Communicating with the 

UNI/59

The UNI/59 connects to the CMnet through 
an EIA-485 CMnet port. A five-pin EIA-485 
port provides two connections to T-Line or U-
Line modules on the Unet. The UNI/59 also 
provides an EIA-232 port for diagnostic 
purposes. You can connect an optional 
BACview

1

 or BACview

2

 keypad display unit to 

the keypad display port (see Figure 2 on page 
3).
 

You must use SuperVision to transfer memory 
to the UNI/59. You can connect a portable 
computer running SuperVision to the UNI/59 
using the module’s Access port. For more 
information about connecting to a 
workstation, refer to “Communicating with 
the Workstation” on page 8.

Connecting to T-Line or U-Line 
modules

The UNI/59 supports up to 59 T-Line or U-
Line modules. If you are using T-Line 
modules, you must use a REPOPT repeater 

after every 20 modules on the Unet. If you are 
using U-Line modules, you must use a 
REPOPT repeater after every 32 modules on 
the Unet. Since the UNI/59 has two Unet 
connections, you do not need a repeater if 
you use 32 or fewer U-Line modules on each 
Unet connection.

NOTE

You cannot combine T-Line and U-

Line modules on the UNI/59.

The baud rate of the Unet is set on the module 
driver Parameter page. Refer to the 

U5I 

Module Driver

 document or 

U5M Module 

Driver 

document for more information.

When using T-Line modules, if the 
communication wires exceed 20 feet in 
length, use a Tnet Protection Board (ALC part 
number TNPB) between the UNI/59 and the T-
Line modules. Refer to the 

TNPB Technical 

Instructions

 for details. 

Automated Logic Corporation recommends a 
specific wire for both power and 
communications on the Unet. This wire, 
which contains a pair of 14AWG wires for 
power and a pair of 22AWG wires for 
communication, is available from:

Magnum Cable Corporation
Cleveland, OH 44110-0500
(800) 421-0820
Product number A3U-LINE

Note that the communication wire is 
unshielded. Shielded cable is not required for 
the Unet.

Use the Unet connection port to connect the 
UNI/59 to the T-Line or U-Line modules. The 
Unet connection port can make two 
connections to the Unet, as shown in Figure 3 
on page 5
. Make sure the Unet connection 
port configuration jumpers are set to UNI and 
EIA-485 (see Figure 4 on page 5). 

Содержание UNI/59

Страница 1: ...r brand and product names are trademarked by their respective companies Technical Instructions UNI 59 Using the UNI 59 2 Specifications 2 Mounting 3 Power Wiring 3 Communicating with the UNI 59 3 Conn...

Страница 2: ...document at http www automatedlogic com or the SupportPlus CD for more information Make sure you use the correct module driver for your application CAUTION Changes or modifications to this unit not ex...

Страница 3: ...100VA maximum Take appropriate isolation measures when mounting the UNI 59 module in a control panel where non Class 2 devices 120VAC or greater or wiring are present You can power several modules fr...

Страница 4: ...modules The UNI 59 supports up to 59 T Line or U Line modules If you are using T Line modules you must use a REPOPT repeater after every 20 modules on the Unet If you are using U Line modules you must...

Страница 5: ...To set the baud rate at 156 kbps when using an ARC156 CMnet set the baud rate jumper to Arc156 see Figure 5 To set the baud rate at 38 4 kbps set the baud rate jumper to 9600 38 4K and set the first...

Страница 6: ...e UNI 59 s module driver and look at the module status report in SuperVision to make sure the module type and number agree with the module The module type for the UNI 59 is 76 To view the module statu...

Страница 7: ...ur own cable use the diagrams in Figure 8 3 Set up your communications program with the correct COM port and baud rate settings to display the diagnostic information output by the UNI 59 The diagnosti...

Страница 8: ...tch s position turn the UNI 59 module off first Once you have adjusted the switch turn the module back on 1 Connect the computer s serial port to the EIA 232 port of the APT using a standard straight...

Страница 9: ...ains the Run and Error LED signals in detail to assist troubleshooting Power indicates power is being supplied to the module CMnet Tx lights when the module transmits data over the CMnet CMnet Rx ligh...

Страница 10: ...ticker on the back of the module also shows the date the module was manufactured The first three characters on the sticker indicate the type of module The next two characters show the year and month o...

Отзывы: