Revised 4/27/00 • UNI/16

3

© 2000 Automated Logic Corporation

You can power several modules from the 
same transformer if you maintain the same 
polarity.

The UNI/16 has an operating range of 
21.6VAC to 26.4VAC. If voltage measured at 
the module’s power input terminals is outside 
this range, the module may not work 
properly.

1. Turn the module’s power off. This 

prevents the module from being powered 
up before the proper voltage is verified.

2. Make sure the 24VAC power source is off.

3. Connect the power wires to the module’s 

power terminals labeled Ground and 
24VAC.

4. Apply power to the transformer.

5. Make sure that 24VAC is present at the 

module’s power input terminals.

6. Set the module’s address. Refer to 

“Addressing” on page 5 for details about 
setting the address.

7. Turn the module’s power switch on.

When the module turns on, the Power, 
Run and Error LEDs turn on and the Run 
and Error LEDs begin blinking. The Error 
LED then turns off. (See “LEDs” on page 7 
for more information about LED signals.) 

Communicating with the 

UNI/16

The UNI/16 connects to the CMnet through 
an EIA-485 CMnet port. A five-pin EIA-485 
port provides two connections to U-Line 
modules on the Unet. You can connect an 
optional BACview

1

 or BACview

2

 keypad 

display unit to the keypad display port (see 
Figure 2).

NOTE

The EIA-232 port, labeled “Diag Port” 

in Figure 2 is reserved for future diagnostic 
capabilities. This feature is not yet available.

You must use SuperVision to transfer memory 
to the UNI/16. You can connect a portable 
computer running SuperVision to the UNI/16 
using the module’s Access port. For more 
information about connecting to a 
workstation, refer to “Communicating with 
the Workstation” on page 6
.

 Figure 2. Module Dimensions and Layout

TYPE: COM3 2

E143900

Open Energy

Management Equipment

88FO

R

Net +

Net -

O p t i o n a l s h i e l d

38.4K

On

1

2

4

8

16

32

64

9600

CMnet baud

Diag transmit

Diag receive

Unet transmit

Unet receive

CMnet transmit

CMnet receive

Error

Run

9600/38.4k

ARC156

port

Access

connection

CMnet

(Module)

Address

CMnet

button

Format

CMnet Mode

Unet 1 Connection

Optional Shield

-

+

-

+

EIA-485

N/C

N/C

N/C

UNI

24 Vac

Ground

Only

Conductors

Use Copper

0.3A

7.2VA

50-60 Hz

24 Vac

Class 2

Use Single Class 2 Only

Off

On

Connector

Power

Indicator

Power

Switch

Power

Port

Diag

gnd

dtr

tx

rx

dcd

5

4

3

2

1

9

8

7

6

n/c

n/c

+10v

n/c

EIA-232

Unet 2 Connection

Auxiliary

device

port

Over ARCNET156 KBaud

BACNet

6 1 /4 "

1 5 .9 cm

1 1/8"

2.9 cm

7 1 /8 "

1 8.1 c m

1 5 /8 "

4 .1 cm

  

   

  

  

   

  

  

 !"

  #   

$  %

  #   

Содержание UNI/16

Страница 1: ...tomated Logic Corporation BACnet is a registered trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions UNI 1 6 Using the UNI 16 2 S...

Страница 2: ...7 2VA power consumption single Class 2 source only 100VA or less Communication One EIA 232 port for diagnostics 9600 bps or 38 4 kbps two EIA 485 ports for Unet communication 9600 bps or 38 4 kbps on...

Страница 3: ...connections to U Line modules on the Unet You can connect an optional BACview1 or BACview2 keypad display unit to the keypad display port see Figure 2 NOTE The EIA 232 port labeled Diag Port in Figure...

Страница 4: ...t the UNI 16 is communicating with the subnet by making sure the Unet transmit and receive LEDs are active When adding a new U Line module to an existing subnet you must transfer memory to the UNI 16...

Страница 5: ...t be made using the Zone GFB option in Eikon Refer to the Eikon User s Guide for more information To transfer GFBs to the UNI 16 you must use SuperVision version 2 6b or later software and you must us...

Страница 6: ...ll equipment has power and is turned on Some devices especially communication devices receive power from a source other than a power cable or adapter for example some devices receive power through com...

Страница 7: ...CMnet Tx lights when the module transmits data over the CMnet CMnet Rx lights when the module receives data from the CMnet Unet receive lights when the module receives data from the Unet Unet transmi...

Страница 8: ...port for the module in SuperVision Refer to the SuperVision User s Guide for more information about the module status report A sticker on the back of the module also shows the date the module was manu...

Отзывы: