Start-Up Checklist

1. Use the appropriate version of Eikon for 

WebCTRL or Eikon 3.0a or later to create 
GFBs for U-Line modules. Be sure to 
enable the Zone GFB option in Eikon for 
WebCTRL or Eikon. Refer to “Writing GFBs 
for the U253” on page 9
 for more 
information.

2. Use the appropriate module driver. (See 

“Job Start-Up” on page 3.)

3. Connect the U-Line modules to the Unet 

and the UNI.

4. Transfer the U-Line modules’ GFBs to the 

UNI. 

Mounting

Screw the U253 into an enclosed panel using 
the mounting holes provided on the cover 
plate. Be sure to leave about 2 inches (5 
centimeters) on each side for wiring.

Addressing

The U253 has dual rotary switches for 
assigning the board address. The top switch 
corresponds to the tens digit and the bottom 
switch corresponds to the ones digit (see 
Figure 2). The U253’s address must be the 
same as its FB number in the UNI. 

For example, if the module’s FB number is 
nine, set the tens switch to zero and the ones 
switch to nine.

The U253’s BACnet Device Instance number 
can be assigned by the UNI or individually 

specified. This number is shown on the UNI 
Properties page in WebCTRL or on the UNI 
Status page in SuperVision.

Power Wiring

The Unet follows the same specifications as a 
legacy CMnet. Refer to the 

Technical 

Handbook

 for details on legacy CMnets. Also 

refer to the 

Technical Handbook

 for detailed 

information on daisy-chain, star, and hybrid 
wiring configurations.

There is a special wire available that contains 
a pair of 14AWG wires for power and a pair of 
22AWG wires for communication. This wire is 
available from:

Magnum Cable Corporation
Cleveland, OH 44110-0500
(800) 421-0820
Product number A3U-LINE

CAUTION

The U253 modules are Class 2 

devices (less than 30VAC, 100VA maximum). 
Take appropriate isolation measures when 
mounting a U253 module in a control panel 
where Non-Class 2 devices (120V and 
greater) or wiring are present.

You can power several modules from the 
same transformer by daisy-chaining the 
power from one U-Line module to the next. 
You must maintain the same polarity. 

Do not exceed 100VA or 500 feet (152.4 
meters) total of 14AWG wire. The maximum 
number of modules on one transformer can 
be figured by dividing the VA of the 
transformer by the sum of the VA of the 
module plus the VA of any accessories. For 
example, if the module’s power is 9VA, 
accessories per module equal 6VA, and the 
transformer is 100VA, you could have up to 6 
modules on the network. See the formula in 
Figure 3 and the example in Figure 4 on page 
5.
 

 Figure 2. Dual Rotary Address Switches

Содержание U253

Страница 1: ...d trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions U253 Using the U253 2 Specifications 2 Job Start Up 3 Job Start Up for WebC...

Страница 2: ...n User s Guide for more information NOTE To operate this module based on a schedule the UNI must be networked with a gateway module U253 modules have been designed to meet low end high volume terminal...

Страница 3: ...NI 16 with the U1M module driver UNI 30 with the U3M module driver UNI 32 with the UNM module driver or UNI 59 with the U5M module driver Eikon 3 0a or later U Line Zone GFBs If you have InterOp Tools...

Страница 4: ...bCTRL or on the UNI Status page in SuperVision Power Wiring The Unet follows the same specifications as a legacy CMnet Refer to the Technical Handbook for details on legacy CMnets Also refer to the Te...

Страница 5: ...s you should have a PROT485 within 250 feet of any U line module on the Unet for surge protection However depending on the frequency of electrical surges in your area the 250 foot recommendation may v...

Страница 6: ...PT using the Supplemental Power 5V dc connection see Figure 6 on page 7 and the special power cable to a laptop keyboard jack or an external supply such as a 5V dc transformer 3 Define the connection...

Страница 7: ...0 5mA maximum sense current when the contacts are closed No pulse accumulation inputs are allowed in U253 FBs except for the override button on the LogiStat Using the LogiStat Use Figure 7 and Figure...

Страница 8: ...utput s operation lock the output to a known condition on the Function Block s Properties page in WebCTRL or the Parameter page in SuperVision then make sure the equipment operates as specified Using...

Страница 9: ...he DRV_UNI16 or DRV_UNI32 module driver For SuperVision systems the U1M U3M UNM or U5M module driver When using a LogiStat sensor with the U253 include a LogiStat microblock and a Zone Control microbl...

Страница 10: ...e in SuperVision LEDs The U253 modules have diagnostic LEDs to assist troubleshooting Table 2 Digital Outputs I O Type Signal Type Channel Number DO 1 Digital 11 DO 2 Digital 12 Table 3 Inputs I O Typ...

Страница 11: ...report for the module in WebCTRL or SuperVision Refer to the appropriate user s guide for more information about the module status report A sticker on the back of the module also shows the date the mo...

Отзывы: