Revised 8/14/02 • U253

5

© 2002 Automated Logic Corporation

The U253 has an operating range of 21.6VAC 
to 26.4VAC. Whenever possible, connect and 
verify power and communications to all 
modules before connecting any inputs or 
outputs.

1. Remove the U253’s power jumper or place 

it in the off position. This prevents the 
module from being powered up before 
verifying correct voltage.

2. Make sure the 24VAC power source is off.

3. Connect the power wires to the module’s 

power terminals labeled 24VAC and Gnd.

4. Turn the 24VAC power source on.

5. Make sure that 24VAC is present at the 

module’s power input terminals.

6. Set the module’s address. Refer to 

“Addressing” on page 4 for details.

7. Replace the module’s power jumper or 

place it in the on position.

When the module turns on, the Run LED 
turns on and begins blinking. The Run 
LED blinks once every two seconds until 
communication is established, then blinks 
twice per second when operating 
normally. Refer to “LEDs” on page 10 for 
more information. 

Communications Wiring

There is a special wire available that contains 
a pair of 14AWG wires for power and a pair of 

22AWG wires for communication. See “Power 
Wiring” on page 4 fo
r details.

Note that the communication wire is 
unshielded. Shielded cable is not required for 
the Unet.

In most circumstances, you should have a 
PROT485 within 250 feet of any U-line 
module on the Unet for surge protection. 
However, depending on the frequency of 
electrical surges in your area, the 250-foot 
recommendation may vary. For example, if 
you have frequent electrical storms in your 
area, you may want to use more PROT485s; if 
you have few electrical storms, you may want 
to use fewer PROT485s. If the entire Unet is 
less than 250 feet, place at least one PROT485 
at the opposite end of the network from the 
UNI. For details about the PROT485, refer to 
the

 ARC156 CMnet Wiring Technical 

Instructions

. Make sure that all modules and 

the PROT485 use the same polarity 
throughout the Unet. You must use a repeater 
after every 32 modules or 3,000 feet.

The Unet baud rate is determined by the UNI 
module and is automatically detected by the 
U253. You can set or change the Unet baud 
rate to 9600 bps or 38.4 kbps on the UNI. The 
U253 begins using the new baud rate after ten 
seconds.

If the module is not communicating with the 
UNI, the module’s color is as follows:

• For WebCTRL systems, the module’s 

color is purple.

• For SuperVision systems, the module’s 

color is coral.

1. Remove the module's power jumper or 

place it in the off position.

2. Check the Unet communication wiring for 

shorts, grounds, or opens.

 Figure 3. Figuring Maximum Number of Modules

 Figure 4. Example of Figuring Maximum Number 

of Modules

VA (transformer)

VA (module) + VA (accessories)

Maximum #

of modules

(rounded down)

=

100VA

9VA + 6VA

=

6.67 or
6 modules maximum

Содержание U253

Страница 1: ...d trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions U253 Using the U253 2 Specifications 2 Job Start Up 3 Job Start Up for WebC...

Страница 2: ...n User s Guide for more information NOTE To operate this module based on a schedule the UNI must be networked with a gateway module U253 modules have been designed to meet low end high volume terminal...

Страница 3: ...NI 16 with the U1M module driver UNI 30 with the U3M module driver UNI 32 with the UNM module driver or UNI 59 with the U5M module driver Eikon 3 0a or later U Line Zone GFBs If you have InterOp Tools...

Страница 4: ...bCTRL or on the UNI Status page in SuperVision Power Wiring The Unet follows the same specifications as a legacy CMnet Refer to the Technical Handbook for details on legacy CMnets Also refer to the Te...

Страница 5: ...s you should have a PROT485 within 250 feet of any U line module on the Unet for surge protection However depending on the frequency of electrical surges in your area the 250 foot recommendation may v...

Страница 6: ...PT using the Supplemental Power 5V dc connection see Figure 6 on page 7 and the special power cable to a laptop keyboard jack or an external supply such as a 5V dc transformer 3 Define the connection...

Страница 7: ...0 5mA maximum sense current when the contacts are closed No pulse accumulation inputs are allowed in U253 FBs except for the override button on the LogiStat Using the LogiStat Use Figure 7 and Figure...

Страница 8: ...utput s operation lock the output to a known condition on the Function Block s Properties page in WebCTRL or the Parameter page in SuperVision then make sure the equipment operates as specified Using...

Страница 9: ...he DRV_UNI16 or DRV_UNI32 module driver For SuperVision systems the U1M U3M UNM or U5M module driver When using a LogiStat sensor with the U253 include a LogiStat microblock and a Zone Control microbl...

Страница 10: ...e in SuperVision LEDs The U253 modules have diagnostic LEDs to assist troubleshooting Table 2 Digital Outputs I O Type Signal Type Channel Number DO 1 Digital 11 DO 2 Digital 12 Table 3 Inputs I O Typ...

Страница 11: ...report for the module in WebCTRL or SuperVision Refer to the appropriate user s guide for more information about the module status report A sticker on the back of the module also shows the date the mo...

Отзывы: