Revised 7/30/02 • S6104
7
© 2002 Automated Logic Corporation
3. Set the Port Select jumper for LogiStat to
enable communications through the
LogiStat Port.
4. In SuperVision, define the connection
using Table 3 on page 8.
5. In SuperVision, set the baud rate at
1200 bps.
6. Attach the LogiStat Adaptor Cable (part
number 235022) to the APT cable. Use this
assembly to connect the APT’s Access
Port to the LogiStat’s LogiPort.
While connected, the LogiStat Pro
displays “LP” indicating that the LogiStat
Pro will not respond to input from the
keypad.
NOTE
When the LogiStat Adaptor Cable
is inserted into the LogiPort, the S6104
can no longer read the LogiStat Inputs.
The S6104 will continue to use the last
valid temperature and setpoint adjust
readings obtained before the cable was
inserted into the LogiPort. If the
Occupancy Override Timer was active
when the connection was made, it will
continue to count down, but no new
inputs can be made until the LogiStat
Adaptor Cable is removed. See the
Eikon
Microblock Reference Guide
for more
information about the LogiStat
microblock.
7. Disconnect the LogiStat Adaptor Cable
from the LogiStat's LogiPort when
finished to allow the S6104 to receive
inputs from the LogiStat.
Communicating Through the Access
Port Using SuperVision
When using SuperVision, you can connect a
workstation or portable computer directly to
the S6104 module using an APT and the
module’s Access Port (see Figure 6). This type
of connection can be used to troubleshoot the
module or transfer memory. If you are using
an ARC156 CMnet, you can receive colors
while connected to a module’s Access Port if
a gateway module is on the CMnet. You
cannot receive alarms through the Access
Port, however.
1. Connect the computer’s serial port to the
APT’s EIA-232 port using a standard
straight-through cable.
2. Set the APT’s Mode Select switch.
• On an ARC156 network segment, use
the TTL setting.
• On a legacy CMnet, use the 485 setting.
3. Connect the APT’s Access Port to the
module’s Access Port.
4. Set the Port Select jumper to Access to
enable communications through the
Access Port.
Figure 5. Port Select to LogiStat
Logi-
Access
Stat
Legacy
Port Select
ARC156
Access Port
LogiStat Port
Temp LS5v
Gnd
Sw
Logi-
Stat
Access
Figure 6. Using the Access Port
EIA-232
Port
9
R x
6 1
2- T x o ut
3 - R x i n
5- G nd
1,6, 8- + 10V or fl oating
T x
+ 5V
APT
5
Ex ec. 4 relay
Isolate
N etw or k
M ode S elec t
T T L
485
A C C E S S
P O R T
Mode Select Switch
Exec. 4 Relay
Switch
Access Port
CONTROL MODULE
Access
Port