5. Check the Baud Select jumper on the 

S6104 for the communication speed of the 
Access Port (9600 or 38.4K). If the jumper 
needs to be changed, turn the module’s 
power off first. The baud rate change 
registers when the module is turned on.

6. In SuperVision, define the connection type 

using Table 3.    

Inputs

 

 

The S6104 provides 10 universal inputs. If you 
are wiring the S6104 module to a LogiStat or 
LogiStat Plus sensor, inputs 9 and 10 can be 
disabled, allowing temperature and setpoint 
adjust inputs to be read through the LogiStat 
Port instead (see “LogiStat Wiring” on 
page 10
). Refer to Table 4 for information 
about wire length, gauge, and shielding. 

 

NOTE

On an ARC156 network segment, 

inputs can be read through a LogiStat, 
LogiStat Plus, or LogiStat Pro. However, on a 
legacy CMnet, inputs can only be read on a 
LogiStat or LogiStat Plus.

• Thermistor: Precon type 2 (10 kohm at 

77°F). Input voltages should range 

between 0.489V and 3.825V for 
thermistors.

 

• 0 to 5VDC: The output impedance must 

not exceed 10 kohms. The input 
impedance of the S6104 is 
approximately 1Mohm.

• 0 to 20mA: The input resistance on the 

A input is 250 Ohms. The B terminal 
supplies a voltage source to power the 
4-20mA transducer. The B terminal is 
capable of supplying 18 to 24VDC, but 
the total current of all B terminals must 
not exceed 200mA. If the voltage 
measured from the B terminal to Gnd is 
less than 18VDC, you need to use an 
additional external power supply.

• Dry Contact: A 5VDC wetting voltage is 

used to detect contact position. This 
results in a 0.5mA maximum sense 
current when contacts are closed. 

 

  

 Figure 7. Port Select and Baud Selects

Table 3. Connection Types

SuperVision

Version

Type of

CMnet

Gateway

Present?

Use Connection 

Type

3.0

any

n/a

Access Port

2.6

ARC156

yes

Direct Connect

2.6

ARC156

no

Direct Network

2.6

legacy

n/a

Direct Network

38.4K

9600

B a u d S e le ct

38.4K

9600

Logi-

Access

Stat

Legacy

P o rt S e le c t

ARC156

A c c e ss P o rt

L o g iS ta t P o rt

Temp LS5v

Gnd

Sw

Logi-

Stat

Access

C M n e t S e le ct

P o rt S e le c t

B a u d S e le ct

Table 4. Input wiring restrictions

Input

Maximum 
Length

Minimum 
Gauge

Shielding

0 to 5VDC

50 feet
15 meters

24AWG

shielded and 
grounded to 
module’s B or 
Gnd terminal

Thermistor
Dry contact

50 feet
15 meters

24AWG

shielded and 
grounded to 
module’s B or 
Gnd terminal

0 to 20 mA

150 feet
46 meters

20AWG

unshielded

LogiStat 
Sensors

100 feet
30 meters

22AWG *

unshielded

*Automated Logic Corporation recommends a specific 
wire to connect the S6104 to the LogiStat. This 22AWG 
solid copper wire is available from Magnum Cable 
Corporation (part number A3LOGISTAT).

Содержание S6104

Страница 1: ...ounting 3 Addressing 3 Power Wiring 4 Network Communications 4 Using the S6104 on an ARC156 Segment 5 Using the S6104 on a Legacy CMnet 5 Connecting the S6104 to the Network 5 Communicating with the W...

Страница 2: ...log outputs A single board provides the power circuitry microprocessor and non volatile memory stores data even during a power failure The Access Port allows communication with WebCTRL or SuperVision...

Страница 3: ...Outputs 6 digital outputs Form A 3A max Analog Outputs 4 analog outputs 0 to 10VDC 20mA source capability Output resolution 8 bit D A Communication For WebCTRL 156 kbps BACnet over ARCNET and 9600 bp...

Страница 4: ...he S6104 has an operating range of 21 6VAC to 26 4VAC If voltage measured at the module s power input terminals is outside this range the module may not work properly 1 Turn the module s power off Thi...

Страница 5: ...lect jumper must also be set to Access NOTE Setting the CMnet jumper to Legacy disables the industry standard BACnet over ARCNET ARC156 protocol for the network segment and enables the proprietary ALC...

Страница 6: ...ommunication speed is fixed at 1200 baud 1 Connect the computer s serial port to the EIA 232 port of the APT using a standard straight through cable 2 Set the APT s Mode Select switch to TTL see Figur...

Страница 7: ...rt when finished to allow the S6104 to receive inputs from the LogiStat Communicating Through the Access Port Using SuperVision When using SuperVision you can connect a workstation or portable compute...

Страница 8: ...ource to power the 4 20mA transducer The B terminal is capable of supplying 18 to 24VDC but the total current of all B terminals must not exceed 200mA If the voltage measured from the B terminal to Gn...

Страница 9: ...e of sensor used Make sure the jumper is positioned correctly and be sure to grip the jumper by the sides only See Figure 10 Figure 8 Input Wiring 15 16 17 18 20 19 14 13 12 11 10 9 8 7 6 5 4 3 2 1 IN...

Страница 10: ...pin 2 Temp of the LogiStat Port The LogiStat Plus also provides the slidepot position and TLO inputs through pin 3 Sw The LogiStat Pro provides temperature setpoint adjust and TLO inputs through seria...

Страница 11: ...mode by setting the HOA switches see Figure 1 on page 2 for the switches location Table 5 on page 12 shows the status of the digital output based on the output s configuration and the HOA switch posit...

Страница 12: ...put s operation lock the output to a known condition using the Function Block s Properties page in WebCTRL or Parameter page in SuperVision Be sure the equipment operates as specified Writing GFBs for...

Страница 13: ...pend on the type of sensor or actuator attached to the I O point You can select the channel number offset and gain using SuperVision s Point Help feature or Configure Points utility Alternatively you...

Страница 14: ...ute Download button If any downloads failed they are listed in the Failures section under the tree in the UI 2 Thermistor 32 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 mA or Volts 32 0 to 20mA 0...

Страница 15: ...SC key type MO module address 15 and press Enter 3 Transfer memory to the module In SuperVision v3 0 click Tools Troubleshooting Transfer Memory to Module In SuperVision v2 6b download memory for This...

Страница 16: ...imal Figure 17 S6104 LED locations Table 9 LED Signals Run LED Error LED Condition 2 flashes per second Off Normal 2 flashes per second 1 flash then pause Normal but module is alone on the CMnet this...

Отзывы: