Revised 7/30/02 • S6104

11

© 2002 Automated Logic Corporation

4. Use Figure 12 to wire a LogiStat, LogiStat 

Plus, or LogiStat Pro to the S6104.  

Strip 1/4 inch of the ends of the wires (see 
Figure 13). 

5. Turn the S6104’s power switch on. 

Digital Outputs

The S6104 has 6 digital outputs which can be 
connected to a maximum of 24 Volts AC/DC 
(see Figure 14). Each digital output is a dry 
contact (rated at 3A maximum).      

Be sure the S6104’s power is off before wiring 
any inputs or outputs. Connect the output 
wiring to the screw terminals on the module.

To verify each output’s operation, lock the 
output to a known condition using the 
Function Block’s Properties page in WebCTRL 
or Parameter page in SuperVision. Be sure the 
equipment operates as specified.

Each digital output can be placed in Manual 
(on or off) or Auto mode by setting the HOA 
switches (see Figure 1 on page 2 for the 
switches’ location). Table 5 on page 12 shows 
the status of the digital output based on the 
output’s configuration and the HOA switch 
position. 

You can monitor the status of the HOA 
switches through WebCTRL or SuperVision. In 
WebCTRL, assign each switch a digital input 
in the FB using the point number and the HOA 
Status Feedback point type. 

In SuperVision, assign each switch a digital 
input in the FB using channel numbers 81 
through 86. Channel 81 corresponds to HOA 
switch number one, channel 82 corresponds 
to HOA switch two, and so on.

An off status means the HOA switch is in Auto 
mode. An on status means the HOA switch is 
in Manual mode.   

 Figure 12. LogiStat Wiring

 Figure 13. Flip Lever Wiring

G

n

d

T

x

R

x

P

w

r

1 2 3 4

LogiStat

S6104

LogiStat Port

Gnd

Sw

Temp LS5v

1

2

3

4

1. Insert wire

into opening

2. Press black

tab down to
connect wire

 Figure 14. Digital Outputs

Power

Auto Off On

1

2

3

4

5

6

7

8

9

10

11

12

DO-3

DO-1

DO-2

DO-4

DO-5

DO-6

Содержание S6104

Страница 1: ...ounting 3 Addressing 3 Power Wiring 4 Network Communications 4 Using the S6104 on an ARC156 Segment 5 Using the S6104 on a Legacy CMnet 5 Connecting the S6104 to the Network 5 Communicating with the W...

Страница 2: ...log outputs A single board provides the power circuitry microprocessor and non volatile memory stores data even during a power failure The Access Port allows communication with WebCTRL or SuperVision...

Страница 3: ...Outputs 6 digital outputs Form A 3A max Analog Outputs 4 analog outputs 0 to 10VDC 20mA source capability Output resolution 8 bit D A Communication For WebCTRL 156 kbps BACnet over ARCNET and 9600 bp...

Страница 4: ...he S6104 has an operating range of 21 6VAC to 26 4VAC If voltage measured at the module s power input terminals is outside this range the module may not work properly 1 Turn the module s power off Thi...

Страница 5: ...lect jumper must also be set to Access NOTE Setting the CMnet jumper to Legacy disables the industry standard BACnet over ARCNET ARC156 protocol for the network segment and enables the proprietary ALC...

Страница 6: ...ommunication speed is fixed at 1200 baud 1 Connect the computer s serial port to the EIA 232 port of the APT using a standard straight through cable 2 Set the APT s Mode Select switch to TTL see Figur...

Страница 7: ...rt when finished to allow the S6104 to receive inputs from the LogiStat Communicating Through the Access Port Using SuperVision When using SuperVision you can connect a workstation or portable compute...

Страница 8: ...ource to power the 4 20mA transducer The B terminal is capable of supplying 18 to 24VDC but the total current of all B terminals must not exceed 200mA If the voltage measured from the B terminal to Gn...

Страница 9: ...e of sensor used Make sure the jumper is positioned correctly and be sure to grip the jumper by the sides only See Figure 10 Figure 8 Input Wiring 15 16 17 18 20 19 14 13 12 11 10 9 8 7 6 5 4 3 2 1 IN...

Страница 10: ...pin 2 Temp of the LogiStat Port The LogiStat Plus also provides the slidepot position and TLO inputs through pin 3 Sw The LogiStat Pro provides temperature setpoint adjust and TLO inputs through seria...

Страница 11: ...mode by setting the HOA switches see Figure 1 on page 2 for the switches location Table 5 on page 12 shows the status of the digital output based on the output s configuration and the HOA switch posit...

Страница 12: ...put s operation lock the output to a known condition using the Function Block s Properties page in WebCTRL or Parameter page in SuperVision Be sure the equipment operates as specified Writing GFBs for...

Страница 13: ...pend on the type of sensor or actuator attached to the I O point You can select the channel number offset and gain using SuperVision s Point Help feature or Configure Points utility Alternatively you...

Страница 14: ...ute Download button If any downloads failed they are listed in the Failures section under the tree in the UI 2 Thermistor 32 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 mA or Volts 32 0 to 20mA 0...

Страница 15: ...SC key type MO module address 15 and press Enter 3 Transfer memory to the module In SuperVision v3 0 click Tools Troubleshooting Transfer Memory to Module In SuperVision v2 6b download memory for This...

Страница 16: ...imal Figure 17 S6104 LED locations Table 9 LED Signals Run LED Error LED Condition 2 flashes per second Off Normal 2 flashes per second 1 flash then pause Normal but module is alone on the CMnet this...

Отзывы: