Analog Outputs

The S6104 module has 4 analog outputs that 
support voltage devices in the 0 to 10VDC 
range. The device that is being controlled 
must have at least 500 Ohms resistance 
measured from its input to ground and must 
share the same ground as the module.   

Although the S6104’s analog outputs were 
not designed to output current, it is possible 
to use these outputs for current mode 
devices. To drive a 20mA device from the 

module’s analog output, the total resistance 
of the load must be 500 Ohms. If necessary, 
wire a 1/2 watt resistor in series with the 
20mA device as shown in Figure 15.

Example:

 To drive a 20mA device that has 

100 Ohms of resistance, wire a 400 Ohm 
resistor in series with the 20mA device (100 
Ohms + 400 Ohms = 500 Ohms total 
resistance). 

Be sure the S6104’s power is off before wiring 
any inputs or outputs. Connect the output 
wiring to the screw terminals on the module.

To verify each output’s operation, lock the 
output to a known condition using the 
Function Block’s Properties page in WebCTRL 
or Parameter page in SuperVision. Be sure the 
equipment operates as specified. 

Writing GFBs for the S6104

You must use Eikon v3.0a or later to create 
GFBs for the S6104. When using a LogiStat 
sensor with the S6104, include a LogiStat 
microblock in the module’s GFB (see Figure 
16)
. The LogiStat microblock supports the 
LogiStat, LogiStat Plus, and LogiStat Pro 
sensors. You do not need to enter point 
numbers or point types in SuperVision or 
Eikon for WebCTRL. Likewise, you do not 
need to enter channel numbers for this 
microblock in SuperVision or Eikon. For more 
information, refer to the 

Eikon Microblock 

Reference Guide

Table 5. HOA Switch Positions

Output 
Configuration

On

Off

Auto

Normally open 
output

DO 
contacts 
closed

DO 
contacts 
open

determined 
by FB 
programming

Results on 
Properties page  
in WebCTRL* or 
Status page in 
SuperVision**

ON

ON

OFF

* use point type of HOA Status Feedback and point 
number

** use channel numbers 81 - 86

 Figure 15. Analog Output Wiring

100

Power

On Off

24 Vac

Gnd

Gnd

Gnd

+

Gnd

+

Gnd

+

+

8

6

5

4

3

1

2

7

AO-4

AO-3

AO-2

AO-1

4-20mA

400

AO

AO

0-10V

Содержание S6104

Страница 1: ...ounting 3 Addressing 3 Power Wiring 4 Network Communications 4 Using the S6104 on an ARC156 Segment 5 Using the S6104 on a Legacy CMnet 5 Connecting the S6104 to the Network 5 Communicating with the W...

Страница 2: ...log outputs A single board provides the power circuitry microprocessor and non volatile memory stores data even during a power failure The Access Port allows communication with WebCTRL or SuperVision...

Страница 3: ...Outputs 6 digital outputs Form A 3A max Analog Outputs 4 analog outputs 0 to 10VDC 20mA source capability Output resolution 8 bit D A Communication For WebCTRL 156 kbps BACnet over ARCNET and 9600 bp...

Страница 4: ...he S6104 has an operating range of 21 6VAC to 26 4VAC If voltage measured at the module s power input terminals is outside this range the module may not work properly 1 Turn the module s power off Thi...

Страница 5: ...lect jumper must also be set to Access NOTE Setting the CMnet jumper to Legacy disables the industry standard BACnet over ARCNET ARC156 protocol for the network segment and enables the proprietary ALC...

Страница 6: ...ommunication speed is fixed at 1200 baud 1 Connect the computer s serial port to the EIA 232 port of the APT using a standard straight through cable 2 Set the APT s Mode Select switch to TTL see Figur...

Страница 7: ...rt when finished to allow the S6104 to receive inputs from the LogiStat Communicating Through the Access Port Using SuperVision When using SuperVision you can connect a workstation or portable compute...

Страница 8: ...ource to power the 4 20mA transducer The B terminal is capable of supplying 18 to 24VDC but the total current of all B terminals must not exceed 200mA If the voltage measured from the B terminal to Gn...

Страница 9: ...e of sensor used Make sure the jumper is positioned correctly and be sure to grip the jumper by the sides only See Figure 10 Figure 8 Input Wiring 15 16 17 18 20 19 14 13 12 11 10 9 8 7 6 5 4 3 2 1 IN...

Страница 10: ...pin 2 Temp of the LogiStat Port The LogiStat Plus also provides the slidepot position and TLO inputs through pin 3 Sw The LogiStat Pro provides temperature setpoint adjust and TLO inputs through seria...

Страница 11: ...mode by setting the HOA switches see Figure 1 on page 2 for the switches location Table 5 on page 12 shows the status of the digital output based on the output s configuration and the HOA switch posit...

Страница 12: ...put s operation lock the output to a known condition using the Function Block s Properties page in WebCTRL or Parameter page in SuperVision Be sure the equipment operates as specified Writing GFBs for...

Страница 13: ...pend on the type of sensor or actuator attached to the I O point You can select the channel number offset and gain using SuperVision s Point Help feature or Configure Points utility Alternatively you...

Страница 14: ...ute Download button If any downloads failed they are listed in the Failures section under the tree in the UI 2 Thermistor 32 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 mA or Volts 32 0 to 20mA 0...

Страница 15: ...SC key type MO module address 15 and press Enter 3 Transfer memory to the module In SuperVision v3 0 click Tools Troubleshooting Transfer Memory to Module In SuperVision v2 6b download memory for This...

Страница 16: ...imal Figure 17 S6104 LED locations Table 9 LED Signals Run LED Error LED Condition 2 flashes per second Off Normal 2 flashes per second 1 flash then pause Normal but module is alone on the CMnet this...

Отзывы: