Revised 9/13/00 • MX16160
7
© 2000 Automated Logic Corporation
Troubleshooting
LEDs
The MX16160 module has several LED
indicators to show the status of certain
functions.
Power - lights when power is being supplied
to the module.
Run - flashes to indicate a normal condition.
Expander Comm - flashes to indicate
expansion bus communications are valid.
Digital Output Status - lights when the digital
output is activated.
Protection
The MX16160 module is protected by internal
solid state Polyswitches on the incoming
power. These Polyswitches are not
replaceable and will reset themselves if the
condition that caused the fault returns to
normal.
Production Date
To determine when a module was
manufactured, check the module status
report for the module in SuperVision. Refer to
the
SuperVision User’s Guide
for more
information about the module status report.
A sticker on the back of the module also
shows the date the module was
manufactured. The first three characters on
the sticker indicate the type of module. The
next two characters show the year and month
of manufacture. (The month digit is in
hexadecimal.)
UI 8
Thermistor
38
-17° to 213° F
-27° to 100.6° C
0.00
0.00
15.88
15.69
mA or Volts
38
0 to 20mA
0 to 5V
§
§
Digital
28
UI 9
Thermistor
39
-17° to 213° F
-27° to 100.6° C
0.00
0.00
15.88
15.69
mA or Volts
39
0 to 20mA
0 to 5V
§
§
Digital
29
UI 10
Thermistor
3A
-17° to 213° F
-27° to 100.6° C
0.00
0.00
15.88
15.69
mA or Volts
3A
0 to 20mA
0 to 5V
§
§
Digital
2A
UI 11
Thermistor
3B
-17° to 213° F
-27° to 100.6° C
0.00
0.00
15.88
15.69
mA or Volts
3B
0 to 20mA
0 to 5V
§
§
Digital
2B
UI 12
Thermistor
3C
-17° to 213° F
-27° to 100.6° C
0.00
0.00
15.88
15.69
mA or Volts
3C
0 to 20mA
0 to 5V
§
§
Digital
2C
UI 13
Thermistor
3D
-17° to 213° F
-27° to 100.6° C
0.00
0.00
15.88
15.69
mA or Volts
3D
0 to 20mA
0 to 5V
§
§
Digital
2D
UI 14
Thermistor
3E
-17° to 213° F
-27° to 100.6° C
0.00
0.00
15.88
15.69
mA or Volts
3E
0 to 20mA
0 to 5V
§
§
Digital
2E
UI 15
Thermistor
3F
-17° to 213° F
-27° to 100.6° C
0.00
0.00
15.88
15.69
mA or Volts
3F
0 to 20mA
0 to 5V
§
§
Digital
2F
UI 16
Thermistor
30
-17° to 213° F
-27° to 100.6° C
0.00
0.00
15.88
15.69
mA or Volts
30
0 to 20mA
0 to 5V
§
§
Digital
20
† Celsius values can only be displayed in SuperVision when the Function
Block is made in Eikon v2.0 or later with the Metric option enabled. Refer to
the Eikon User’s Guide for more information.
§ Use the Point Configuration or Point Help feature available in SuperVision
v2.0 or later.
Table 4. Input Channel Numbers
Point
Signal Type
Channel
Number
†Range Offset
Gain