background image

 
 
 

18947_ins_alc_wireless_temp_xmtr 

Automated Logic Corporation 
1150 Roberts Boulevard 
Kennesaw, GA 30144 

LS3-WT 

Installation and Operating Instructions 

Rev 03/07/2008 

Phone: (770) 429-3000 

Fax: (770) 429-3001 

http://www.automatedlogic.com 

Analog Output Module Training 

1.

 

Apply power to the receiver and output modules. 

2.

 

The power LED on the Receiver should light and remain lit.  The powered analog output module's LED should 
flash and go out.  (The flash is very quick.) 

3.

 

Remove the cover of the transmitter and remove battery tabs or install the batteries, observe polarity. (See Figure 1)  
The small LED at the bottom right, next to the Transmitter Training Button in Figure 1, should flash approximately 
once every 10 seconds.  (The flash is very quick.) 

4.

 

Pick a transmitter and an analog output module you want to train to recognize one another. Press and hold the 
plastic service button on the top of the Output Module, at the same time press for one second and release the button 
on the transmitter.  When the LED on the output module lights, release its button (The LED will go out when you 
release the button).  The output module will now report the environmental conditions from the transmitter trained to 
it.  The output module's LED will quickly flash whenever it receives an update from the transmitter. 

5.

 

Mount the transmitter at the desired location.  If needed, remove the batteries to do so.  The units will remain 
trained to one another through power failures and battery replacement. 

6.

 

Replace the transmitter's cover and back out the security screws. 

Diagnostics 

 

Possible Problems: 

Possible Solutions: 

Temperature is reading its low 
limit 

-

 

Check wire from output modules to controller for proper connections and 
polarities. 

 

-

 

Check to see if the controller's software is configured properly. 

 

-

 

Check transmitter to see if its LED flashes about every 10 seconds.  If not 
replace the batteries. 

 

-

 

Check power to the receiver and output module. 

 

-

 

Check output modules LED, if it is blinking fast  

Check the associated transmitter's batteries 

Retrain the modules 

 

Temperature reading is coming out 
the wrong output module 

 

-

 

Retrain the modules. 

 

Temperature is reading incorrectly 

 

-

 

Check wire from output modules to controller for proper connections and 
polarities. 

 

-

 

Check to see if the controller's software is configured properly. 

 

-

 

Check to see if the correct output module is connected to the right controller. 

 

Specifications 

 

Supply Power: BA/LI3620.  

Two 3.6V Lithium batteries, 

5 to 8 year battery life at 10 second transmit rate 

Inputs: 

Built in thermistor 

Accuracy: 

±0.2 °C 

Transmitted Range: 

-40° to 85°C 

Environmental Operation Range:

  

Temp: 0° to 60°C 
Humidity: 5% to 95% RH non-condensing

 

Material: 

ABS Plastic 

Material Rating: 

UL94 V-0 

Radio Frequency: 

418 MHz or 433MHz 

Transmitter Interval: 

~10 seconds 

Antenna: 

Built inside the enclosure 

FCC Approval: 

FCC ID# T4F16963N16964  

(418MHz only) 

 

 