Automated Logic LGE Скачать руководство пользователя страница 5

Revised 12/22/99 • LGE

5

© 1999 Automated Logic Corporation

• the Assigned Subnet Mask

• the Default Gateway Addr

4. Log out of SuperVision and set the IP Addr

DIP switch to Assigned.

5. Turn the LGE’s power on.

6. If using SuperVision v2.6, edit your HOSTS

file to include the following line for each
gateway (see

TCP/IP Setup for SuperVision

for a detailed procedure):

IP Address LGx

Where IP Address is the address assigned
by the Network Administrator and x is the
gateway’s LGnet address.

7. If using SuperVision v2.6, run Setup.exe

on the disk shipped with your LGE.

This setup copies updated Portman files to
your emsys folder

8. Configure your connections page for

Network in SuperVision Plus v3.01 and
later, or NetBIOS in SuperVision v2.6.

Wiring

Power Wiring

The LGE has an operating range of 21.6VAC to
26.4VAC. If voltage measured at the module’s
power input terminals is outside this range,
the module may not work properly.

CAUTION

The LGE module is a Class 2

device (less than 30VAC, 100VA maximum).
Take appropriate isolation measures when
mounting the LGE module in a control panel
where non-class 2 devices or wiring are
present.

You can power several modules from the
same transformer if you maintain the same
polarity.

1. Turn the module’s power off. This

prevents the module from being powered
up before the proper voltage is verified.

2. Make sure the 24VAC power source is off.

3. Connect the power wires to the module’s

power terminals labeled Ground and
24VAC (see Figure 1 for location).

4. Apply power to the transformer.

5. Make sure that 24VAC is present at the

module’s power input terminals.

6. Set the module’s LGnet address. Refer to

“Addressing” on page 3 for details about
setting the address.

7. Turn the LGE’s power switch on and verify

that the Run and Error LEDs are blinking.
Verify that the Error LED turns off and the
Run LED continues blinking (see Table 3
on page 8 
to troubleshoot the LEDs).

Communications Wiring

When communicating at 156 kbps, the CMnet
uses a unique implementation of the industry
standard ARCNET protocol called ARC156.
For a summary of the differences between
ARCNET and ARC156, please refer to the

ARC156 CMnet Wiring Technical Instructions

.

Use the appropriate wire for CMnet
communications. When communicating with
the ARC156 protocol, use an A3ARC156 wire
available from:

Magnum Cable Corporation
Cleveland, OH 44110-0500
(800) 421-0820

Use a dedicated 22AWG to 18 AWG twisted
pair (EIA-485) for legacy CMnet wiring. For
more information about CMnet wiring, refer
to the

Technical Handbook

or to

ARC156

CMnet Wiring Technical Instructions

.

Connecting to the CMnet

1. Turn off the power.

2. Connect the CMnet wires to the LGE’s

screw terminals as shown in Figure 4 on
page 6
. Be sure to follow the same

Содержание LGE

Страница 1: ...Corporation InterOp is a trademark of Automated Logic Corporation BACnet is a registered trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical I...

Страница 2: ...ion The LGE uses the CEM module driver for more information see the CEM Module Driver document on the Automated Logic website at www automatedlogic com CAUTION Changes or modifications to this unit no...

Страница 3: ...net Console Port 1 and Ethernet communications errors running and power Memory 1 MB flash 1 MB RAM Protection Built in surge and transient protection circuitry Battery 7 year lithium BR2325 battery pr...

Страница 4: ...d the local network segment Assigned When the IP Addr DIP switch is set to Assigned you must set the above parameters on the CEM Parameter page Use the following procedure to set the IP address when u...

Страница 5: ...s the module from being powered up before the proper voltage is verified 2 Make sure the 24VAC power source is off 3 Connect the power wires to the module s power terminals labeled Ground and 24VAC se...

Страница 6: ...erVision v3 0 click Tools Troubleshooting Module Status To view the module status report in SuperVision v2 6b press the Esc key type MO module address 15 and press Enter 3 Transfer memory to the modul...

Страница 7: ...l the Error LED flashes three times in sync with the Run LED 4 Release the Format button 5 Transfer memory to the module Refer to Transferring Memory on page 6 Figure 5 Wiring Diagrams Figure 6 Using...

Страница 8: ...ion Refer to the SuperVision User s Guide for more information about the Module Status report A sticker on the back of the module also shows the date the module was manufactured The first three charac...

Отзывы: