Revised 12/22/99 • LGE

8

© 1999 Automated Logic Corporation

LEDs

The LGE has several LED indicators to show
the status of certain functions. Table 3 on
page 8 
explains the Run and Error LED
signals in detail to assist troubleshooting. See
Figure 1 on page 2 for location of LED signals.

Power - indicates power is being supplied to
the module.

CMnet transmit - indicates that the LGE is
transmitting data over the CMnet.

CMnet receive -indicates that the LGE is
receiving data from the CMnet.

Console transmit - indicates that the Console
Port is transmitting data.

Console receive - indicates that the Console
Port is receiving data.

Link- indicates communication through the
Ethernet port.

Lan - blinks to indicate network activity.

Protection

The LGE is protected by internal solid state
Polyswitches on the incoming power and
network lines. These Polyswitches are not
replaceable and will reset themselves if the
condition that caused the fault returns to
normal.

Production Date

To determine when a module was
manufactured, check the Module Status
report in SuperVision. Refer to the

SuperVision

User’s Guide

for more information about the

Module Status report.

A sticker on the back of the module also
shows the date the module was
manufactured. The first three characters on
the sticker indicate the type of module. The
next three characters show the year, month,
and week of manufacture. (The month digit is
in hexadecimal.)

Table 3. LED Signals

Run LED

Error LED

Condition

2 flashes
per second

Off

Normal

2 flashes
per second

1 flash per
second

Normal, but module is
alone on the CMnet

2 flashes
per second

2 flashes
alternating
per second

Five minute auto-restart
delay after system error

2 flashes
per second

2 flashes in
sync per
second

Module is configured for a
different baud rate than the
rest of the CMnet

2 flashes
per second

3 flashes
per second

Module has just been
formatted

2 flashes
per second

4 flashes
per second

Two or more items in the
database have the same
ARC156 CMnet address

2 flashes
per second

On

Exec halted after frequent
system errors

5 flashes
per second

On

Exec start-up aborted, Boot
is running

5 flashes
per second

Off

Firmware transfer in
progress

7 flashes
per second

7 flashes
per second

Ten second recovery
period after brownout

14 flashes
per second

14 flashes
per second

Brownout

Содержание LGE

Страница 1: ...Corporation InterOp is a trademark of Automated Logic Corporation BACnet is a registered trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical I...

Страница 2: ...ion The LGE uses the CEM module driver for more information see the CEM Module Driver document on the Automated Logic website at www automatedlogic com CAUTION Changes or modifications to this unit no...

Страница 3: ...net Console Port 1 and Ethernet communications errors running and power Memory 1 MB flash 1 MB RAM Protection Built in surge and transient protection circuitry Battery 7 year lithium BR2325 battery pr...

Страница 4: ...d the local network segment Assigned When the IP Addr DIP switch is set to Assigned you must set the above parameters on the CEM Parameter page Use the following procedure to set the IP address when u...

Страница 5: ...s the module from being powered up before the proper voltage is verified 2 Make sure the 24VAC power source is off 3 Connect the power wires to the module s power terminals labeled Ground and 24VAC se...

Страница 6: ...erVision v3 0 click Tools Troubleshooting Module Status To view the module status report in SuperVision v2 6b press the Esc key type MO module address 15 and press Enter 3 Transfer memory to the modul...

Страница 7: ...l the Error LED flashes three times in sync with the Run LED 4 Release the Format button 5 Transfer memory to the module Refer to Transferring Memory on page 6 Figure 5 Wiring Diagrams Figure 6 Using...

Страница 8: ...ion Refer to the SuperVision User s Guide for more information about the Module Status report A sticker on the back of the module also shows the date the module was manufactured The first three charac...

Отзывы: