Revised 7/10/01 • InterOP8500
16
© 2001 Automated Logic Corporation
Table 6. Input Channel Numbers
Point
Signal Type
Channel
Number
†Range Offset
Gain
UI 1
RTD
51
-50° to 250° F
-46° to 121° C
0.00
0.00
15.25‡
mA or Volts
31
4 to 20mA
0 to 5V
§
§
Digital
71
UI 2
RTD
52
-50° to 250° F
-46° to 121° C
0.00
0.00
15.25‡
mA or Volts
32
4 to 20mA
0 to 5V
§
§
Digital
72
UI 3
RTD
53
-50° to 250° F
-46° to 121° C
0.00
0.00
15.25‡
mA or Volts
33
4 to 20mA
0 to 5V
§
§
Digital
73
UI 4
RTD
54
-50° to 250° F
-46° to 121° C
0.00
0.00
15.25‡
mA or Volts
34
4 to 20mA
0 to 5V
§
§
Digital
74
UI 5
RTD
55
-50° to 250° F
-46° to 121° C
0.00
0.00
15.25‡
mA or Volts
35
4 to 20mA
0 to 5V
§
§
Digital
75
UI 6
RTD
56
-50° to 250° F
-46° to 121° C
0.00
0.00
15.25‡
mA or Volts
36
4 to 20mA
0 to 5V
§
§
Digital
76
UI 7
RTD
57
-50° to 250° F
-46° to 121° C
0.00
0.00
15.25‡
mA or Volts
37
4 to 20mA
0 to 5V
§
§
Digital
77
UI 8
RTD
58
-50° to 250° F
-46° to 121° C
0.00
0.00
15.25‡
mA or Volts
38
4 to 20mA
0 to 5V
§
§
Digital
78
UI 9
RTD
59
-50° to 250° F
-46° to 121° C
0.00
0.00
15.25‡
mA or Volts
39
4 to 20mA
0 to 5V
§
§
UI 10
RTD
5A
-50° to 250° F
-46° to 121° C
0.00
0.00
15.25‡
mA or Volts
3A
4 to 20mA
0 to 5V
§
§
UI 11
RTD
5B
-50° to 250° F
-46° to 121° C
0.00
0.00
15.25‡
mA or Volts
3B
4 to 20mA
0 to 5V
§
§
UI 12
RTD
5C
-50° to 250° F
-46° to 121° C
0.00
0.00
15.25‡
mA or Volts
3C
4 to 20mA
0 to 5V
§
§
UI 13
RTD
5D
-50° to 250° F
-46° to 121° C
0.00
0.00
15.25‡
mA or Volts
3D
4 to 20mA
0 to 5V
§
§
UI 14
RTD
5E
-50° to 250° F
-46° to 121° C
0.00
0.00
15.25‡
mA or Volts
3E
4 to 20mA
0 to 5V
§
§
UI 15
RTD
5F
-50° to 250° F
-46° to 121° C
0.00
0.00
15.25‡
mA or Volts
3F
4 to 20mA
0 to 5V
§
§
† Celsius values can only be displayed in SuperVision when the Function
Block is made in Eikon v2.0 or later with the Metric option enabled. Refer to
the Eikon User’s Guide for more information.
§ Use the Point Configuration or Point Help feature available in SuperVision
v2.0 or later.
‡ Any adjustments needed to calibrate the RTD are done as offset adjustments
in the microblock.
Table 7. Maintained Binary Output
Channel Numbers across sections 1 and 3
Johnson Channel “xA”
(wired across terminal sections 1 and 3)
ALC Channel
1A
11
2A
12
3A
13
4A
14
5A
15
6A
16
7A
17
8A
18
Table 6. Input Channel Numbers
Point
Signal Type
Channel
Number
†Range Offset
Gain