![Autolux UNI/L version Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/autolux/uni-l-version/uni-l-version_quick-manual_3021458007.webp)
7
2.2 General Wiring Specifications
Connect as shown below.
A suitably qualified person must make all wiring connections.
Please refer to the following wiring connection drawings (see 2.3) and
observe the notes referring to cable type and length. Failure to follow these
guidelines may result in electrical interference or unsatisfactory operation.
When making connections to screw terminals please ensure that no more
than 6mm of insulation is stripped back and that no stray wire strands escape.
0-12V outputs, Analogue 0 – 10V output and remote switch inputs for
occupancy, push switch and panic switch should be connected by 0.75mm
2
cable of maximum length 100m.
The remote light level sensor(s) and remote temperature sensor can be sited
up to 100m from the control; the cable may be screened to improve noise
rejection. Cable resistance must be less than 10 Ohms to minimise errors.
Connect the screen to the ground terminal (GND).
All sensor and signal wiring should be kept separate from mains wiring to
minimise noise pick-up.