t1 Extend
Time Read/Write 06 00
to
60
Extend maximum allowed time in
units of 10 minutes, e.g. “09”
allows 90 minutes. Setting 00
effectively disables the function.
t2 PIR
/
Press
switch
Runback time
Read/Write 20 00
to
99
PIR runback time in minutes.
Applies to all PIR sensor inputs.
Setting 00 allows connection of On
/ Off switches where no time delay
is applied.
t3 Lux
Change
Delay time
Read/Write 30 00
to
99
LUX level relay change delay time
in seconds.
1=Zone 1 only active
2=Zones 1 and 2 active
3=Zones 1, 2 and 3 active
4=Zones 1, 2, 3 and 4 active
5=Zones 1, 2, 3, 4 and 5 active
6=All zones active
E1 Active
Zones Read/Write 06 00
to
06
Note: If E1 is set to 6 then S6 is
automatically set as 0.
0 = sensor is PIR
sensor/pushbutton/switch input
S1 Sensor
1
Configuration
Read/Write 01 00
to
01 1 = sensor is LUX sensor input
0 = sensor is PIR
sensor/pushbutton/switch input
S2 Sensor
2
Configuration
Read/Write 01 00
to
01 1 = sensor is LUX sensor input
0 = sensor is PIR
sensor/pushbutton/switch input
S3 Sensor
3
Configuration
Read/Write 00 00
to
01 1 = sensor is LUX sensor input
0 = sensor is PIR
sensor/pushbutton/switch input
S4 Sensor
4
Configuration
Read/Write 00 00
to
01 1 = sensor is LUX sensor input
0 = sensor is PIR
sensor/pushbutton/switch input
S5 Sensor
5
Configuration
Read/Write 01 00
to
01 1 = sensor is Panic switch input
0 = sensor is PIR
sensor/pushbutton/switch input
1 = sensor is temperature sensor
input
S6 Sensor
6
Configuration
Read/Write 00 00
to
01
Note: If S6 is set to 1 then E1 is
automatically limited to 5.