Tension Controller TC818
8.2 Troubleshooting
Appearance of failure
Solution
The controller does not work
after powered on
Incorrect calculation of radius
No output
Measurement fails, display
“A/D error”
Measurement fails, display
“sigl error”
The power supply is 110-264 VAC.
1. Check the connection of power supply.
2. Replace new fuse(4A).
1.Set proper values for the radius calc. related parameters.
2.Use proximity switch or encoder with NPN signal
3.Check connection or replace new proximity switch or
encoder
1.Press the
OUTPUT ON/OFF button
to turn on
2.Switch
off, switch on after 30 seconds
3.Connect the drive unit properly
power
In need of repair
1.Select the right range for Signal[26
]
2.Check the connections and signal, replace new
sensor.
Possible malfunction
Power fails or fuse fused.
1.The setting of radius calc. related parameter is incorrect.
2.Wrong proximity switch/encoder.
3.proxmity switch/encoder damaged or incorrect connection.
1. Output has been turned off
2. Output short-circuit protection
3. Incorrect connection of Reel A and Reel B
A/D IC damaged
1. Signal range and sensor do not match
2. Sensor fails or incorrect connection.
The keys and digital knob
do not work
The controller does not start
after MC1 is on
Can't switch to automatic
mode
Tension too high or too low
after restarting
Setting tension(SV) changes after
switching from manual mode to
automatic mode
Check the
Lock
indicator, if the indicator
keypad is locked. Press
LOCK
key to unlock.
is on, the
1. Disable the Sync. Mode[42
switch must be mounted on the main reel while
enabled and set right value for Start Freq.[03].
2. Set right value for Action Mode[41].
] function. The proximity
1. Check sensor, connections, parameters and
recalibrate until getting the correct measurement
2. Keypad locked, press
LOCK
key to unlock.
1. Keep the MC1 off before stopping
2. keep the MC4 on
This is normal, it makes the smooth transition.
Keypad has been locked
1. Sync. Mode[42] is enabled.
2. Bad value for Action Mode[41].
The automatic/manual switching is disabled
when error appears
1.The measured tension is incorrect
2.Keypad locked
1. MC1 is on when system stop
2. MC4 is off, output memory is disabled
While switching the controller from manual
mode to automatic mode, the measured
tension before switching will be used as the
setting tension for automatic control
Measurement fails, display
“over range”
1.Recalibrate
2.Check connections and signal, replace new sensor.
3.Set Sensor
[
24] according to real condition.
1. Invalid calibration
2. Sensor fails or incorrect connection
3. Bad value for Sensor[24].
Not stable in manual and
automatic mode
Stable in manual mode but
not stable in automatic mode
1. Reinstall
2. Use the appropriate drive unit
3. Use the appropriate sensor and recalibrate
1. Use the appropriate sensor and recalibrate
2. Use the appropriate drive unit
3. Alter the value of these three parameters
1. Tension sensing roller out of roundness,
bearing damaged, roller bended.
2. Bad clutch/brake or driver
3. Signal fails or incorrect calibration
1. Bad type of tension sensor.
2. Bad type of clutch, brake or driver.
3. Bad value for Prop. Band[05], Inte. Time[06]
and Dead Band[07]
38