2 Set-Up and Connections
设置和连接
10.08.2015
Mk7 D.T.I. Set-Up GuideMk7
数据传输接口设置指南
Page 19
Figure 2.2.3.v Boiler Setup
图
2.2.3v
锅炉设置
In the Boiler Setup screen, the type of burner can be configured, whether it is a standalone D.T.I. or
with the M.M., and also if it taking data from the E.G.A.
在锅炉设置屏幕上可以设置燃烧器类型,无论燃烧器是否是独立的数据传输接口或控制模
块或是否从尾气分析仪获取数据。
If an E.G.A. is being used together with the M.M., than the D.T.I. will receive the E.G.A. data from the
M.M. For Mk8
E.G.A.’s, the D.T.I. must be set to ‘EGA Direct’.
如果尾气分析仪与控制模块共同使用,数据传输接口将从控制模块接收尾气分析仪数据。如是
Mk8
尾气分析仪,则数据传输接口必须设为
“EGA Direct”
。
Once the Boiler Setup has been configured press
.
锅炉设置完成后按下
按钮。
To copy a boiler configuration, enter the Boiler Configuration screen, and press
.
复制锅炉配置时需要进入锅炉配置屏幕,然后按下
按钮。
Select the boiler to be copied, and assign a new ID number for the new boiler.
选择需要复制的锅炉,然后为新锅炉分配一个新
ID
号。
Note:
For the Mk8
E.G.A.’s with the M.M.’s, the E.G.A. must be wired to both the M.M. and the
D.T.I., see section 2.1.4 for the wiring diagram.
注:至于带有控制模块的
Mk8
尾气分析仪,尾气分析仪必须同时连接控制模块和数据传输接
口。见
2.1.4
节的接线图。