7.4 Analog Channels
All analog input channels shall be connected directly to the I/O module. Connect either a
4-20 mA signal or a 0-10 V signal per channel.
From the wiring diagram, locate the correct I/O module and connect as follows.
7.5 Output Channels
The I/O Cabinet comes with a set of standard output channels. In addition, optional output
channels may be installed.
7.5.1 Standard Output Channels
The following output channels are always available in the I/O Cabinet.
7.5.2 Optional Output Channels
All switch output channels shall be connected directly to the I/O module. From the wiring
diagram, locate the correct I/O module and connect as follows.
Page 48 (49)
Analog channel
0-10 V
4-20 mA
1
00 – 10
20 – 30
2
01 – 11
21 – 31
3
02 – 12
22 – 32
etc.
...
...
# Function
Connections
Description
1 Buzzer Active
00 – 10
Activates on new events.
Deactivates on
– acknowledge of event, OR
– press the Alarm button
2 Common Unacknowledged
Events
01 – 11
Active if at least one unacknowledged event
is present.
3 Common Active OR
Unacknowledged Events
02 – 12
Active if at least one active OR at least one
unacknowledged event is present.
4 <None>
03 – 13
5 <None>
04 – 14
6 <None>
05 – 15
7 <None>
06 – 16
8 <None>
07 – 17