L U X S E T U P
Note: For loads which should turn on regardless of ambient
light levels, set Lux to maximum (Photocell inactive).
It is best to set Lux when the ambient light level is at the
required minimum level.
Set Lux to the minimum and wait for the load to switch off.
Without shadowing the PIR (from daylight), slowly increase
Lux whilst waving your hand below the PIR until the lighting
load switches on.
T I M E S E T U P
The Time adjuster should be set appropriately for the usage of
the area, for example some possible settings could be:
Offi ces with workers regularly walking 20 minutes
Offi ces with mainly desk based workers 40 minutes
Corridors
5 minutes
Washrooms with total coverage
10 minutes
Washrooms with entry coverage only
40 minutes
2D fi ttings*
20 minutes (min)
* Not less than 20 minutes due to potential lamp failure. If in doubt contact
your lamp manufacturer.
With Time set to maximum (40 minutes) it halves at each point
as moved towards minimum i.e. From max to min: 40, 20, 10,
5, 2.5 minutes, 80, 40, 20, 10 seconds.
P R E C A U T I O N S
• Do not place the PIR near heat sources, fans or in ventilated
ceiling voids.
• These PIRs can be wired in parallel (sharing the same Live,
Switch Line and Neutral) however:
- Some lamps emit Infra Red radiation, if these are nearby
and switched via another PIR switch the PIR may false
trigger.
• Do not place close to, or positioned such that, any light
source points directly into the PIR.
• Ensure wires and cables are securely held within the
connection terminals.
• Do not connect on a circuit with large inductive loads, as
induced spikes may cause false triggering or damage the
PIR.
• The PIR should be protected by a 5 or 6 Ampere mcb or
fuse.
•
Disconnect the PIR from the circuit before performing
insulation testing of the wiring circuit.
T E C H N I C A L D E TA I L S
Voltage:
220 - 240Vac, 50Hz
Loading:
1000W of Resistive loads
750W of Fluorescent loads
750W of Transformer loads
750W of CFL, LED and 2D lamps
Minimum load: 2W resistive, suitable for most
energy saving lamps, LEDs and
emergency fi ttings
IP rating:
IP20
Detection range: 360 degrees with 5m diameter when
mounted at a 2.4m ceiling height
Time:
10 seconds to 40 minutes in 9 steps
Lux:
10 to 1000 lux and maximum (photocell
inactive) at the PIR switch.
3 YEAR W A R R A N T Y
This Surface mounted PIR switch comes
with a 3 year warranty from the date
of manufacture and is CE marked.
IF YOU EXPERIENCE PROBLEMS WHICH CANNOT BE
RESOLVED BY THE TROUBLE SHOOTING PAGE PLEASE
RETURN THE PIR TO YOUR SUPPLIER WITH DETAILS OF THE
FAULT, LOAD AND APPLICATION.