Dynamic Series
Part D: ARM receiving unit
Malfunction signalled by the receiving unit
D - 12
The STATUS LED is
on.
Over-current in one of
the PWM analogue
outputs.
Contact the support service of the
machine manufacturer.
The RUN LED blinks.
The receiving unit
does not send com-
mands in the CAN net-
work.
Contact the support service of the
machine manufacturer.
The ERR LED blinks.
CAN communication
error.
Contact the support service of the
machine manufacturer.
The SETUP LED
blinks once.
Error on the address
key.
Contact the support service of the
machine manufacturer.
The SETUP LED
blinks twice.
Error on the data mem-
ory.
Replace the data memory on the DTK
connector with the backup data mem-
ory attached inside the cover (see
chapter 7).
The SETUP LED
blinks slowly.
A data memory is con-
nected to the BKK con-
nector.
If you are not performing a backup of
the data memory, remove the memo-
ry from the BKK connector (see
chapter 7).