7 | Requirements at the installation location
EN
Operating manual Clou Compact 2.0
72
7
Requirements at the installation location
7.1
Safety distances to be observed
b
b
c
a
Fig. 7:
Safety distances
Safety distances to be observed (minimum distances – see
also type plate).
• a) 1000 mm (at the front in the radiation area)
• b) 250 mm (at the sides in the radiation area)
• c) 150 mm (rear)
For corner installation:
• a) 1000 mm (at the front in the radiation area)
• b) 200 mm (at the sides in the radiation area)
7.2
Combustion air
An adequate supply of combustion air must be provided during operation. With a modern very thick
building shell it can happen that the combustion air supply is not guaranteed for balanced flue opera-
tion or that the draft behavior is impaired. In this case an adequate supply of combustion air must be
provided. Your Austroflamm specialist dealer will be happy to advise you.
TIP
Ensure that combustion air openings are not closed!
7.3
Chimney requirements
When connecting the flue pipes to the chimney, national and/or local safety regulations must be com-
plied with. Your Austroflamm stove is fitted at the factory with a flue pipe outlet at the top (diameter
150 mm). The connection can, as described in these instructions, be rearranged to the bottom. When
connecting with other pipe diameters the approval of your responsible chimney sweep is required.
The flue pipe connection and flue pipe transitions must be sealed accordingly. Your Austroflamm spe-
cialist dealer knows the guidelines and will be happy to advise you. For your own safety the connection
of the flue pipe must be carried out by a technically competent person.
7.4
Floor load-bearing capacity
Before installing, verify whether the load-bearing capacity of the substructure can withstand the weight
of your Austroflamm stove.
7.5
Floor condition
In the radiation area of the pane (in front of the stove), the floor must not be combustible.
7.6
Room of installation
Note that the room in which the stove is installed must have at least one door / one window leading to
the outside, or be directly connected to such a room. For balanced flue operation, other heating appli-
ances and extractor hoods must not be operated together with this heating appliance as part of the
room air system.