www.austin-hughes.com
UM-MB-Q221V1
P.9
< 1.6 > Outlet Control
1. Outlet Schedule ( Time )
Outlet schedule provides a way for you to switch on / off or repower ( OFF then ON ) an individual
outlet or group of outlets at a specifi c time on one-time, daily or weekly basis.
Step 1. Enable the rule
Step 2. Enter the “
Name
“ of the rule. ( min. 1 / max. 48 char. )
Step 3. Select “
Time
“ from “
Trigger
“
Step 4. Select the outlet(s) you want to monitor and the trigger will act upon
Step 5. Select “
Action
“ ( ON / OFF / “ Cycle – Off then On “ )
Step 6. Enter the “
Cycle time
“ ( for “
Cycle – Off then On
“ power control type ONLY ). It defi nes the time waiting for
switching ON the outlet(s) after being switched OFF. ( Default : 10s, min. 1s ~ max. 999s )
Step 7. Select “
One-time / Daily / Weekly
“ from “
Cyclic
“
Step 8. Select “
Date
“ & “
Time
“ for One-time / “
Time
“ for Daily / “
Weekday
“ & “
Time
“ for Weekly.
Step 9. Click “
Apply
“ to save the settings.