Mark the holes’ position and align the wire coming from the wall in the hole beside the
connectors.(see picture)
•
Drill two holes and insert the plastic anchors carefully into the holes until they are flush with the
wall.
•
Fasten securely the thermostat to the wall with the two screws.
Connecting the Wires
The AURATON 1300 thermostat can be used with single stage heating system. Inside the
thermostat, three terminals which label COM(common), NC(normal close) and NO(normal open)
would be found. In most case, COM and NO are used.
Temperature Span
Span is the temperature difference between the turn ON and OFF temperature. The factory pre-set
span is ±0.5°C. For example, control temperature setting is 20°C. The heater will be operated when
the room temperature drops to 19.5°C and will be turned off when the temperature rises to 20.5°C.