4
Assembly Instruction
KS 15 S12
01
By attaching the drive to a movable
element of the window a so-called
“power-operated window” is created
which, according to the Machinery
Directive 2006 / 42 / EG, represents a
machine.
Pay attention to possible hazards on
tilting or rotating windows, whose
secondary closing edges are located
at less than 2,5 m installation height ab-
ove the fl oor, under consideration of the
Control Unit and usage!
n
ote
w
Arning
i
ntenDeD
uSe
Area of application / Scope of application
This drive is intended for the electromotive opening and
closing of windows in facade and roof areas.
The main task of this product
, in combination with
a window and a suitable external control unit,
is to
evacuate hot smoke and combustion gases in case
of fi re
, to safe human lives and protect material
assets. Furthermore, with the electromotive operated
window and a suitable external control unit,
the natural
ventilation
of the building can be ensured.
Intended use according
The drive is intended for stationary installation and
electrical connection at the window as part of a building.
The drive is in combination with an external Control Unit
(e.g. from
a
umüller
) released for its proper use at a
power-operated window for the following use:
• Application for natural ventilation
with an installation height of the drive and
the bottom side of sash of at least 2,5 m above
the
fl
oor,
or
with an opening width at the HSK of the driven
part of < 200 mm by a simultaneous speed of
< 15 mm/s at the HSK in closing direction.
• Application as NRWG (natural smoke and heat
exhaust ventilator(s) for ventilation without dual
purpose for ventilation in accordance with EN12101-2.
The need for a risk assessment at the installation site
due to the reasonably foreseeable misuse.
A risk assessment in accordance with the Machine-
ry Directive 2006 / 42 / EG
for the usage of the power-
operated window
for natural ventilation is absolutely
necessary
under the following conditions:
• the installation height of the drive and lower edge
of casement < 2,5 m above the fl oor
and
one of the following conditions:
• the opening width at the HSK > 200 mm,
or
• the closing speed at the HSK is > 15 mm/s,
or
• the opening speed at the HSK is > 50 mm/s,
or
• the closing force at the HSK is > 150 N
The following fl ow chart can be applied, which also includes
the protective measures in accordance with EN 60335-2-
103/2016-05.
We as manufacturers are well aware of our duties and
responsibilities regarding the development, manufactu-
ring and placing of safe window drives on the market and
consistently implement them. Ultimately, however, we have
no direct infl uence on the usage of our drives. Therefore,
as a precaution, we point out the following:
• The
constructor or his agent
(architect, specialist
planner)
are obligated
to evaluate the
hazards to persons
, outgoing from the usage,
installation position, opening parameters and from the
external Control Unit of the power operated window,
already
in the planning phase and to establish
necessary protective measures
.
• The
constructor / manufacturer
of the machine
“power-operated window”
must implement
the
planned
protective measures
at the installation site
or, if not yet established,
determine them
by it´s
own responsibility and detect or
minimize possible
remaining risks
.