Aumuller FTA600 DF Скачать руководство пользователя страница 27

27

Assembly Instruction

FTA 600 

Problem

Possible causes

Possible solutions

Drive does not 
start

•  Duration of mains

power supply too short

•  Drive run direction not

correct

•  Connecting cable not

connected

•  Power supply / Control

Unit voltage incorrect, 
too high or too low (see 
data sheet)

•  No mains supply to

power supply unit /
Control Unit 
(no voltage)

•  Drive has shut down

on overload 

•  Adjust supply voltage

as specifi ed in the 
technical documen-
tation

•  Check drive cables

change polarity

•  Check all connection

cables

•  Check power supply unit

and replace if necessary

•  Connect power supply

•  First move drive in 

CLOSE direction

Drive doesn‘t 
start after 
having been 
in operation 
several times

•  Operating time has been 

exceeded, drive has 
been overheated

•  See possible solutions

above associated with 
„Drive doesn‘t start“

•  Wait until drive has

cooled down and start 
again

•  See possible solutions

associated with: 
“Drive doesn‘t start“

Drive doesn‘t 
close

• Safety mechanism has 
 been 

triggered

•  See possible solutions

above associated with 
„Drive doesn‘t start“

•  Release safety area for

operation and briefl y 
move the drive in OPEN 
direction

•  See possible solutions

associated with: 
“Drive doesn‘t start”

Drive travels 
uncontrolled in 
open and close 
direction

• Residual 

ripple 

of 

power

     supply / control unit too   
      hight

•  Fault in power supply 

unit / Control Unit

•  Adjust drive voltage to

the required value of 
drive. (values see data 
sheet of drive)

•  Check output voltage of

power supply unit or 
Control Unit

Door release 
contact does not 
switch

• Contakt 

defect

• Faulty 

programming

•  Sending drive for

repair

•  Check voltage and

current consumption
of the door opener

• Check 

programming

with UniPC

M

AINTENANCE

 

AND

 

REPAIR

07

H

ELP

 

IN

 

CASE

 

OF

 M

ALFUNCTIONS

, R

EPAIRS

 

AND

 

M

AINTENANCE

Professional repair of a defect drive can only be performed at the
manufacturer’s factory or manufacturer-certifi ed specialist company.
Unauthorized opening or manipulation of the drive terminates warranty.

1.   Exchange defect drives or have them repaired by the manufacturer.
2.   In case of problems during installation or normal operation the
 

following table might be useful:

M

AINTENANCE

 

AND

 

MODIFICATION

To ensure continuous function and safety of the drive periodic maintenan-
ce by a specialist company is required at least once a year (as mandated 
by law for smoke and heat exhaust systems). Operational readiness must 
be checked regularly. Frequent inspection of the system for imbalance 
and signs of wear or damages of cables and fastening elements must be 
performed. 
During maintenance contaminations must be removed from the drive. 
Fastenings and clamping screws must be checked for tightness. Test runs 
during the opening and closing procedure of the devices must be per-
formed.
The drive itself is maintenance-free. Defect devices may only be repaired 
in our factory. Only replacement parts of the manufacturer may be used. 
When the connection cable of this device is damaged it must be replaced 
by the manufacturer or his customer service or a similarly qualifi ed per-
son to avoid endangerment. 
It is recommended to conclude a maintenance contract. A sample main-
tenance contract can be downloaded from the homepage of

Firm Aumüller Aumatic GmbH

 

(

www.aumueller-gmbh.de

). 

While cleaning the windows, drives may not have direct contact with 
water or cleaning agents. Drives must be protected from dirt and dust 
during the construction phase or renovations.

Maintenance process

1.

  Open or extend power-operated casement completely.

2.

  Completely disconnect the system from the mains and secure it 

 

against automatic or manual activation.

3.

  Check windows and fi ttings for damages.

4.

  Check all mechanical fastenings (if required, observe information on

 

torques in installation instructions). 

5.

  Check electric drives for damages and contaminations.

6.

  Check connecting cables (drive cable) for:

 

- tightness of the cable screw

 

- functionality of the strain relief

 - 

damages

7.

  Check the mobility of hinges and fi ttings and re-adjust or apply

 

lubricant, e.g. silicone spray (observe the instructions of the manu-

 

facturer of this window system).

8.

  Check peripheral seal, remove contaminations or replace. 

9.

  Perform cleaning to maintain functionality (e.g. clean extending

 

elements of the drive, such as chains or spindles by damp wiping them 

 

with acid or lye-free agents and drying them and, if required, lubricate 

 

them with cleansing oil e.g., Ballistol).

10.

 Turn on operating voltage.

11.

 Open and close the power-operated window via the operating

 

voltage (functional test). 

12.

 If available, check and re-adjust protection systems of the safe guard

 

fi xture.

13.

 Check the intactness of the CE label at the power-operated system 

 

(e.g. SHEV/Natural smoke and heat exhaust ventilators).

14.

 Check the intactness of warning instructions and labels at the

 respective 

drive. 

15.

 Perform a risk assessment in accordance with Machinery Directive

 

2006 / 42 / EG, if required, e.g. after modifying the machine.

Содержание FTA600 DF

Страница 1: ...FTA600 R FTA600 DF FTA600 GF FOLDING ARM DRIVES according to Machinery Directive 2006 42 EC annex VI Assembly and Commissioning Instructions...

Страница 2: ...ON STEP 4B FTA600 R Hinge side mounting inward opening door INSTALLATION STEP 4C FTA600 DF Hinge side mounting inward opening side hung window INSTALLATION STEP 4D FTA600 GF Opposite hinge side mounti...

Страница 3: ...G AND SAFETY SYMBOLS IN THESE IN STRUCTIONS The symbols used in the instructions shall be strictly observed and have the following meaning Caution Warning Danger due to electric current Caution Warnin...

Страница 4: ...0 mm by a simultaneous speed of 15 mm s at the HSK in closing direction Application as NSHEV natural smoke and heat exhaust ventilators for ventilation without dual function for ventilation in accorda...

Страница 5: ...oor ZAA 20 1 Opening at HSK 200 mm and Speed at HSK CLOSE 15 mm s OPEN 50 mm s 20 ZAA 2 Yes Yes No No Risk covered by Declaration of Conformity for window drives Observe danger at NSK 2 5 m above floo...

Страница 6: ...connection assignment the electrical supply data see machine plate and performance limits see technical data as well as the mounting and installation instructions of the drive must be strictly observe...

Страница 7: ...h a trial run It shall be ensured that drive and casement are set correctly and that security systems if available are functioning properly After the installation of the system is completed the end us...

Страница 8: ...ive shall only be operated with control devices from the same manufacturer There is no liability warranty or customer service if third party parts are used Exclusively original replacement parts of th...

Страница 9: ...ir intlets Internal intelligent cut off switch S12 Programmable contact for door opener Unitary plug solution for all AUM LLER chain drives and AUM LLER folding arm drives Options Programmable special...

Страница 10: ...temperature range 5 C 75 C MA Torque OPEN 215 Nm 600 N MZ Torque CLOSE 215 Nm 600 N FH Pullout force 3000 N fastening depended Lever arm aluminium RAL9006 Connecting cable with plug non halogen grey...

Страница 11: ...gent cut off switch S12 Programmable contact for door opener Unitary plug solution for all AUM LLER chain drives and AUM LLER folding arm drives Options Programmable special functions M COM for automa...

Страница 12: ...losing edges Space on the frame above min 56 max 106 mm Space on the frame above min 40 mm Space on the frame above min 48 mm Space on the frame min 60 mm on the casement min 40 mm door width 1200 mm...

Страница 13: ...ins spind les of the drives must be extendable or retractable easily The casement must run smoothly and the weight must be in balance The test procedure of drives may only be performed on a non slip a...

Страница 14: ...llowing conditions must be fulfilled for the instal lation of the drives so they can be properly assembled with other parts and constructed to a complete machine at the window without impairing the sa...

Страница 15: ...profile depth PT and door hinge dimension B 05 MOUNTING FTA600 R DRILL HOLES ACCORDING TO MOUNTING VARIANTS FTA600 R OPPOSITE HINGE SIDE MOUNTING OUTWARD OPENING DOOR INSTALLATION STEP 3 INSTALLATION...

Страница 16: ...IDE MOUNTING INWARD OPENING DOOR 05 INSTALLATION STEP 4B MOUNTING FTA600 R 260 400 422 5 5 x8 408 M5 x4 50 20 5 24 40 4 11 22 33 4 1x Angle L 422 50 x 40 x 4 1x Angle L 100 50 x 75 x 5 with slots 1x A...

Страница 17: ...R FTA600 R Ensure that the role of the folding arm drive FTA600 R when opening and closing is based on the angle K88 K88 K88 K88 door leaf door frame 1 2 3 Space A A View from inside FTA600 R M5 105 5...

Страница 18: ...5 6 8 35 30 6 6 20 6 5 6 9 70 130 130 408 70 24 22 11 33 M4 M5 RA 1 FTA600 DF 9 05 MOUNTING FTA600 DF 1x Angle L 422 50 x 40 x 4 1x Bolt 14 x 57 x M10 1x Lever arm 14 x 12 x 30 1x Eyebolt M8 1x Caseme...

Страница 19: ...mm 81 15 mm 81 10 mm 79 0 mm 77 10 mm 76 20 mm 75 30 mm 05 MOUNTING FTA600 DF 36 47 10 40 20 35 25 X B X X 4 400 356 24 35 13 6 4 40 2 20 17 35 X X 13 5 10 X 4 X X 400 386 24 35 13 6 13 5 1 40 0 2 20...

Страница 20: ...e angle of frame bracket K104 at the frame M5 Fasten folding arm drive FTA600 GF on the angle with the screws Fit slide rail with screws M5 at the casement Using the screws and lock washers and mount...

Страница 21: ...F 10 10 11 11 Insert the circlip for stabilization in the drill hole Push bolt in the connector Insert this module in slide rail Using the screw and mount the drive arm of the folding arm drive FTA600...

Страница 22: ...A FL BD BD AK FL Cable crossover without protective cable hose Cable crossover with protective cable hose Connection cable routing on the hinge side Make sure that during opening or closing procedure...

Страница 23: ...grey GY WH is used for communication in systems with synchronized multi drive operation Standard CLOSE Optional OPEN contact max 24 V 500 mA min 10mA ELECTRIC CONNECTION ELECTRIC CONNECTION from contr...

Страница 24: ...the housing cover with the both screws Locking hooks at the housing cover prevent withdrawal of the plug under tensile load Five terminals to 1 5 mm2 The performances especially the fire be havior of...

Страница 25: ...acket 0 C 70 C 45 x 17 x 6 mm 3 wires 0 5 mm x 50 mm Feature Equipment printed circuit board with connecting wires for in tegration in site supplied junction box Cable junction box for renewal Order n...

Страница 26: ...accessibility Ensure expansion possibilities of the drive and the drive cable Consider the cable length of drives Operation of the power operated window When operating the power operated window safety...

Страница 27: ...diness must be checked regularly Frequent inspection of the system for imbalance and signs of wear or damages of cables and fastening elements must be performed During maintenance contaminations must...

Страница 28: ...s to the country in which the product has been acquired The warranty includes material and manufacturing defects incurred during normal use The warranty period for delivered material is twelve months...

Страница 29: ...29 Assembly Instruction FTA600 CERTIFICATES 08...

Страница 30: ...30 Assembly Instruction FTA600 CERTIFICATES 08...

Страница 31: ...ensure that the data and information are as correct and up to date as possible we still cannot guarantee that they are free from mistakes and errors All information and data contained in this document...

Страница 32: ...n Tel 49 8271 8185 0 Fax 49 8271 8185 250 info aumueller gmbh de 9000017000_V0 1_KW05 14 www aumueller gmbh de AUM LLER AUMATIC GMBH Gemeindewald 11 86672 Thierhaupten Tel 49 8271 8185 0 Fax 49 8271 8...

Отзывы: