11.5.
Mechanical position indicator: set
1.
Move valve to end position CLOSED.
2.
Turn lower indicator disc until symbol
(CLOSED) is in alignment with the
mark on the cover.
3.
Move actuator to end position OPEN.
4.
Hold lower indicator disc in position and turn upper disc with symbol
(OPEN)
until it is in alignment with the mark on the cover.
5.
Move valve to end position CLOSED again.
6.
Check settings:
If the symbol
(CLOSED) s no longer in alignment with mark on the cover:
→
Repeat setting procedure.
11.6.
Switch compartment: close
1.
Clean sealing faces of housing and cover.
2.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the sealing faces.
3.
Check whether O-ring [3] is in good condition, replace if damaged.
4.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
➥
5.
Place cover [1] on switch compartment.
6.
Fasten screws [2] evenly crosswise.
38
SGM 04.1 – SGM 14.1 / SGMR 04.1 – SGMR 14.1
Commissioning (basic settings at actuator)
Profibus DP
Содержание SGM 04.1
Страница 55: ...55 SGM 04 1 SGM 14 1 SGMR 04 1 SGMR 14 1 Profibus DP...
Страница 56: ...56 SGM 04 1 SGM 14 1 SGMR 04 1 SGMR 14 1 Profibus DP...
Страница 59: ...59...