15.
Test run
15.1 Checking the
direction of rotation
.
Place indicator disc on shaft.
The direction of rotation of the indicator disc (figure M) indicates the direc-
tion of rotation of the output drive.
.
Move actuator manually to intermediate position or to sufficient distance
from end position.
.
Switch on actuator in running direction CLOSE and observe the direction
of rotation:
If the indicator disc turns clockwise, the direction of rotation is correct.
If the direction of rotation is wrong, switch off immediately
Correct phase sequence at motor connection. Repeat test run.
15.2 Checking the limit switching
.
Move actuator manually into both end positions of the valve.
.
Check whether limit switching is set correctly. Hereby observe that the
appropriate switch is tripped in each end position and released again after
the direction of rotation is changed. If this is not the case, the limit
switching must first be set, as described from page 16.
If no other options (sections 16. to 18.) require setting:
.
Close switch compartment (see page 24, section 19.).