Faults and Warnings: See page 59, clause 17.
15.8.2 Menu indications
Parameters with the wild card "x" in the submenu can be
indicated and changed:
x = 0 : indicate only (grey background)
x = 1 : indicate and change (white background)
(only possible in selector switch position OFF)
To change a parameter, a password must first be entered (see page 22).
27
Part-turn actuators SG 03.3 – SG 04.3
Operation instructions
with AUMATIC AC 01.1
Subgroup
Parameter
name
Sub-
menu
Standard
value
Min/M
ax
Valuetext
Note
M0
LANGUAGE/CONTRAST
LANGUAGE/CO
NTRAST
LANGUAGE
M0X0
0
0
GERMAN
LCD language
1
ENGLISH
LCD CONTRAST
M0X1
80
0
LCD contrast (percent), the higher
the value, the darker the display
(see page 19)
100
M1
SETTINGS
M11
SEATING
MODE
OPEN POSITION M11X0
0
0
LIMIT
Switching off in end positions
(only limit seating permitted)
(see page 55, subclause 16.9)
1
TORQUE
CLOSED
POSITION
M11X1
0
0
LIMIT
1
TORQUE
M13
LOCAL
CONTROLS
MAINTAINED
LOCAL
M13X0
3
0
OFF
Push-to-run operation or self-
retaining in operation mode
LOCAL
Push-to-run = OFF
(see page 55, subclause16.10)
1
OPEN
2
CLOSED
3
OPEN + CLOSE
(STOP)
4
OPEN + CLOSE
(NO STOP)
Indication
VALUETEXT
Note
S3
NOT READY IND.
CLEAR STATE
Only for actuators with Profibus DP interface:
The actuator has received a GC CLEAR telegram. In this
state the actuator can not be operated from REMOTE. Help:
Send GC OPERATE.
NOT REMOTE
Selector switch not in position REMOTE. Help: Set selector
switch to position REMOTE
WRONG COMMAND
Only for actuators with bus interface: Several run commands
were received simultaneously (e.g. OPEN and CLOSE) or
the max. nominal value has been exceeded.