Lamp test
After the supply voltage is connected a function test of the LEDs is
automatically performed. All 5 LEDs must be illuminated for at least
3 seconds.
15.5 General information about
the menu design
The indications on the display are divided into 3 main groups:
1) group
S
= Status indications
, 15.5.3
2) group
M
= Menu indications
, see 15.5.4
3) group
D
= Diagnosis indications
, see 15.5.5
In the upper right corner of the display the group in which one is moving is
indicated. See example figure S1, page 20: Group
S
= Status indications
15.5.1 LCD contrast setting
.
Either: Change setting via menu "
LANGUAGE/CONTRAST
" (see "Change
settings" below)
.
Or: Press button
in the status page
S0
and hold it. After approx. 10 s
(the above mentioned menus - groups
S
,
M
,
D
- are hereby skipped) the
brightness of the LCD display continuously changes from bright to dark
and vice versa. When the button is released, the current brightness level
is saved under "
CONTRAST
".
15.5.2 Navigation through the indications
(Selector switch in position OFF or REMOTE)
Scrolling within a group:
.
To scroll within a group (see subclause 15.5):
Press push button "scroll"
,
. The triangles
in the display show
the direction of the scrolling.
Confirm selection:
.
To reach a new menu or a subgroup:
Load the new selection with the push button "Confirm selection"
.
Select group
S
,
M
or
D:
After the AUMATIC is switched on, the status indication S0 is shown on the
display.
.
Change from the group
S
(Status indications
S0,S1,S2,S3
) to the
group
M
(Menu indications):
Press
and hold it for approx. 2 seconds until the group
M0
appears.
.
Change from the group
S
(Status indications
S0,S1,S2,S3
) to the
group
D
(Diagnosis indications):
Press
and hold it until the group
D0
appears (menu indications M are
skipped).
.
Change from any group
M
or
D
back to the group
S0
:
Press push button
briefly.
Show settings:
.
Set selector switch to position OFF or REMOTE.
.
Select group
M0
.
.
Make selection: e.g.
M0
"
LANGUAGE/CONTRAST"
and
confirm selection with
.
.
"Select "
VIEW
" and confirm with
.
Change settings:
.
Set selector switch to position OFF.
.
Select group
M0
.
.
Make selection: e.g.
M0
"
LANGUAGE/CONTRAST
" and
confirm selection with
.
.
"Select "
EDIT
" and confirm with
.
.
Enter password (see page 22 ).
.
Change value.
Cancel process/back:
.
To cancel a process or to go back to the previous indication:
Press push button
.
19
Part-turn actuators SG 03.3 – SG 04.3
Operation instructions
with AUMATIC AC 01.1
C
C
C
C
C