Default value:
No signal
Setting values:
No signal
A: Signal behaviour Off. Position is not signalled.
C________|¯¯¯¯¯¯¯¯O
B: Signal is active from reaching the position up to 360°.
C¯¯¯¯¯¯¯¯¯|_______O
C: Signal is active from 0° until the position is reached.
C_______|¯|_______O
D: When passing the position, a pulse signal is issued. The pulse range (range +/–
around the pivot point) depends on the set hysteresis.
Figure 69: Signal behaviour of positions
Information
The set signal behaviour is valid for all positions.
10.1.12. Hysteresis for signalling intermediate positions: set
The hysteresis determines the tripping point.
Example
Parameter
Position 4 M1153
is set to 180° (50 % of the travel).
Parameter
Hysteresis M1148
is set to 3.0°.
Figure 70: Switching behaviour for signalling behaviours B, C, D and hysteresis 3.0°.
P1
Switch-on point (
●
)
P2
Switch-off point (
○
)
pT
Pulse duration = 2 times XT + hysteresis
Required user level:
AUMA (6)
.
Customer settings M0041
Multiport valve M1140
Hysteresis M1148
57
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive Modbus TCP/IP
Commissioning (basic settings)