Operation manual Profibus PBD 100
23.07.2007
25/36
LED 'Bus Err' (V6) ?
Voltage supply of PROFIBUS DP
board correct?
PROFIBUS DP
communication correct
LED 'DataEx'
illuminated
(V8)?
Incorrect parameter
data. Correct
parameter in master
Incorrect
configuration data.
Correct
configuration in
master
Adress on slave
set > 125
Check PROFIBUS DP
master
No
Yes
1
PROFIBUS DP slave not in
mode Data Exchange
No baud rate
found
blinking
once
Master only functions
on level 2. Does not try
to program or configure
blinking
twice
blinking
three times
continously
illuminated
not
illuminated
- Ckeck master
- Check wiring
- Check bus connection
2