Process signification input
Bit
Designation
Value
Description
0
Is OPEN
Limit
seating in end
position OPEN
1
0
1 Limit switch in OPEN direction operated.
otherwise
1
Is CLOSED
Limit seating in end
position CLOSED
Is CLOSED
Torque seating in
end position
CLOSED
1
0
1
0
Limit switch in CLOSE direction operated.
otherwise
Torque switch and limit switch in direction
CLOSE operated.
otherwise
2
Is NOMINAL
1
0
Nominal value position is within max. error variable (outer dead band).
Signal occurs only if PROFIBUS master has set nominal operation
otherwise
3
Not used
Reserved for extensions
4
Runs OPEN
1
0
Run command (OPEN or NOMINAL) from PROFIBUS in direction
OPEN is executed. For operation in stepping mode, this signal is also
active during an off-time, the dead time and the reversing prevention.
No operation is carried out via the PROFIBUS.
5
Runs CLOSE
1
0
Run command (CLOSE or NOMINAL) from PROFIBUS in direction
CLOSE is executed. For operation in stepping mode, this signal is also
active during an off-time, the dead time and the reversing prevention.
No operation is carried out via the PROFIBUS.
6
Warning
1
0
One or several warnings have been given (at least one bit set in
warning-byte)
No warnings are active (all bits cancelled in warning byte).
7
Faults
1
0
One or several faults have occurred so that the actuator
can no longer be controlled via PROFIBUS (at least
one bit set in fault-byte).
No faults are active (all bits cancelled in fault-byte).
Bit
Designation
Value
Description
0
Th
(optional)
1
0
A thermal fault (motor thermal protection) has occurred.
No thermal fault has occurred.
1
1
STE
(power failure)
1
0
A power failure has occurred: Phase failure
No power failure has occurred.
2
Selector sw
REMOTE
Always remote
1
0
Selector switch in position REMOTE.
Selector switch not in position REMOTE.
3
Selector sw.
LOCAL
Not available
1
0
Selector switch in position LOCAL
Selector switch not in position LOCAL.
4
WÖL
1
0
Limit switch OPEN left operated.
Limit switch OPEN left not operated.
1
Limit switch CLOSE right active.
Byte 1: Logic run