AUMA MATIC Operation Instructions 

AUMA Actuators, Inc. USA

 

 
AUMA MATIC Compacts consist of motor controls, local controls (optional) and other control elements, which are 
required to operate an electric actuator 
 

Scope

 

 
These instructions are intended to cover the AUMA MATIC compact in both the C and S configuration with an 
AUMA interface board.  These instructions are for general startup and basic troubleshooting 
 
For calibration/setting of optional Electronic Positioner 601 or Pulse Timer, refer to the appropriate instructions. 
 

Electrical Connections

 

 

 

CAUTION:

  Observe safety regulations. 

 

• 

Verify that the motor and control voltages correspond with equipment supplied.  Refer to the nameplate on 
motor and/or AUMA MATIC Compact.39 

• 

Attach conduit or cables following approved practices. 

 

 

CAUTION:

  Appropriate conduit and sealing methods must be followed to ensure the NEMA rating for the 

 enclosure 

furnished 

 

• 

Connect field wiring according to wiring diagram supplied.  If drawing is not available, contact the nearest 
AUMA office with the Sales Order Number located on the actuator nameplate.  A replacement drawing will be 
provided. 

• 

Actuator limit switches and optional RWG (position feedback transmitter), if supplied, should be set using 
appropriate setting instructions prior to proceeding. 

 
The AUMA MATIC Compact contains a programmable logic board.  The following DIP switch settings are made 
on the logic board.  The factory has preset the logic board switches per the order requirements, if requested, prior 
to shipment. 
 

Dip Switch S1

 

 

Position 1:

  Limit switch seating in the closed direction. 

Position 2:

  Torque seating in the closed direction. 

Note:

  Limit switch closed must be set just prior to the torque seating position for closed indication or a fault  

 will 

occur. 

 

Closed direction is clockwise output of electric actuator.  For counter clockwise seating options consult factory.

 

 
Dip Switch S2

 

 

Position 1:

  Seal-in circuit remote close 

Position 2:

  Seal-in circuit remote open 

Position 3:

  Seal-in circuit local close 

Position 4:

  Seal-in circuit local open 

Position 5:

  Optional blinker switch off 

Position 6:

  Torque switch included in collective fault signal 

All information in this document is subject to change without notice.

 

 
ISSUE 02/02 

Page 1 of 4 

SE-SI-35-0001 