AUMA Matic Positioner 

Calibration Instruction 

AUMA Actuators, Inc. USA

 

 

Electrical Connections 

 

 

CAUTION:

  Observe safety regulations. 

 

• 

Verify that the motor and control voltages correspond with equipment supplied.  Refer to the nameplate on 
motor and/or AUMA MATIC Compact. 

• 

Attach conduit or cables following approved practices. 

 

 

CAUTION:

  Appropriate conduit and sealing methods must be followed to ensure the NEMA rating for the 

 enclosure 

furnished 

 

• 

Connect field wiring according to wiring diagram supplied.  If drawing is not available, contact the nearest 
AUMA office with the Sales Order or Serial Number located on the actuator nameplate.  A replacement 
drawing will be provided. 

NOTE:

  ACTUATOR LIMIT SWITCHES MUST BE SET USING APPROPRIATE SETTING INSTRUCTIONS 

 

PRIOR TO PROCEEDING. 

 
 

 

 

Compartment

Cover 

       Positioner Board 

Logic Board 

Power Supply 

 

Monitor Control 

Board 

 
 

Figure 1 

AUMA MATIC Controller 

 

All information in this document is subject to change without notice.

 

 

ISSUE 02/02 

Page 2 of 11 

SE-SI-35-0007 

 

Содержание Matic Series

Страница 1: ...ontrol Accurate positioning is attained through the use of a precision position feedback potentiometer or current device RWG current transmitter The controller drives the motor reversing starters whic...

Страница 2: ...he NEMA rating for the enclosure furnished Connect field wiring according to wiring diagram supplied If drawing is not available contact the nearest AUMA office with the Sales Order or Serial Number l...

Страница 3: ...que seating in the clockwise direction Switch S3 2 In position 1 the actuator is set for limit seating in the counterclockwise direction In position 2 the actuator is set for torque seating in the cou...

Страница 4: ...orrect Verify the field wiring matches electrical drawing supplied by AUMA Fuses are open CAUTION Before checking replacing fuses ensure all power is disconnected Remove selector switch push button co...

Страница 5: ...ent FINE SENSITIVITY This control adjustment determines the amount of error signal that occurs before the Sens P7 motor is energized in the direction determined by the input signal This is only used f...

Страница 6: ...in end position CLOSED refer to Figure 3 LEDs are not illuminated Turn potentiometer 0 P3 slightly clockwise until LED V27 yellow lights up LED V28 green is illuminated Turn potentiometer 0 P3 slight...

Страница 7: ...To prevent exceeding the max permissible number of starts refer to Technical data sheet SG SAR or consult factory in extreme cases a time delay between 0 5s left stop and 10s right stop may be set wit...

Страница 8: ...ow lights up LED V27 yellow is illuminated Turn potentiometer max P4 clockwise until LED V27 yellow goes out Then turn potentiometer max P4 slightly counter clockwise until LED V27 yellow lights up ag...

Страница 9: ...ioner and set according to the specified nominal value E1 After setting for Split Range operation perform further readjustment as described in Calibration section Page 6 Figure 4 Positioner board A7 S...

Страница 10: ...3 4 5 0 5v 0 5v 3 ON ON 1 2 3 4 5 1 2 3 4 5 0 5v 4 20 mA ON ON 1 2 3 4 5 1 2 3 4 5 0 10v 0 5v ON ON 1 2 3 4 5 1 2 3 4 5 4 20 mA 0 5v 3 ON ON 1 2 3 4 5 1 2 3 4 5 Fail close 4 20 mA 4 20 mA ON ON 1 2 3...

Страница 11: ...diately after loss of E1 and remains in this position Fail close Actuator runs to the closed position after loss of E1 Fail open Actuator runs to the open position after loss of E1 2 Signals from inte...