AUMA Matic Positioner 

Calibration Instruction 

AUMA Actuators, Inc. USA

 

 

All information in this document is subject to change without notice.

 

 

 

Possible LED indication: 

(refer to Figure 3)

 

Required setting in end position OPEN 

(refer to Figure 3) 

LEDs are not illuminated 

Turn potentiometer ”0” (P3) slightly clockwise until 
LED 

 (V28 green) lights up. 

LED 

 (V27 yellow) is 

illuminated 

Turn potentiometer ”0” (P3) slightly clockwise until LED 

 (V27 

yellow) goes out and LED 

 (V28 green) lights up. 

If

 

LED 

 (V28 green) is 

illuminated 
 

Then

 

Turn potentiometer ”0” (P3) counter-clockwise until LED 

 (V28 

green) goes out. 
Then turn potentiometer ”0” (P3) slightly clockwise until LED 

 

(V28 green) lights up again. 

 
 

Positioner Adjustment End Position CLOSED (inverse operation) 

 

• 

Run actuator with push-button 

 (local controls) to 

end position CLOSED

• 

Connect max. command signal (nominal value E1) = 20 mA. 

 

Possible LED indication: 

(refer to Figure 3)

 

Required setting in end position CLOSED 

(refer to Figure 3) 

LEDs are not illuminated 

Turn potentiometer ”max” (P4) slightly counter-clockwise until 
LED 

 (V27 yellow) lights up. 

LED 

 (V27 yellow) is 

illuminated 

Turn potentiometer ”max” (P4) clockwise until LED 

 (V27 

yellow) goes out. 
Then turn potentiometer ”max” (P4) slightly counter-clockwise  
until LED 

 (V27 yellow) lights up again.  

If

 

LED 

 (V28 green) is 

illuminated 

Then

 

Turn potentiometer ”max” (P4) slightly counter-clockwise until 
LED 

 (V28 green)  goes out and LED 

 (V27 yellow)  lights 

up. 

 
 

Positioner in Split Range version (option) 

 
For Split Range a modified version of the positioner is used.  The standard version is not suitable for Split Range 
operation. 
 

Split Range: description of functions 
 

Split Range allows the adaptation of the positioner to nominal value ranges which are for example necessary to 
individually control several actuators (up to four actuators) with the same nominal value signal. Typical values for 
two actuators are 0 - 10 mA and 10 - 20 mA or 4 - 12 mA and 12 - 20 mA.  But all other values between 0/4 - 20 
mA can also be set and adjusted. 
 

Split Range Programming 
 

Programming of the positioner at the code switches S1-7, S2-7, S3-7 can, with the exception indicated below, be 
performed in the same manner as for normal operation. 

NOTE:  Switch S1-7 DIP 5 at code switch S1-7 must always be in position ON for Split Range version. 

ISSUE 02/02 

Page 8 of 11 

SE-SI-35-0007 

 

Содержание Matic Series

Страница 1: ...ontrol Accurate positioning is attained through the use of a precision position feedback potentiometer or current device RWG current transmitter The controller drives the motor reversing starters whic...

Страница 2: ...he NEMA rating for the enclosure furnished Connect field wiring according to wiring diagram supplied If drawing is not available contact the nearest AUMA office with the Sales Order or Serial Number l...

Страница 3: ...que seating in the clockwise direction Switch S3 2 In position 1 the actuator is set for limit seating in the counterclockwise direction In position 2 the actuator is set for torque seating in the cou...

Страница 4: ...orrect Verify the field wiring matches electrical drawing supplied by AUMA Fuses are open CAUTION Before checking replacing fuses ensure all power is disconnected Remove selector switch push button co...

Страница 5: ...ent FINE SENSITIVITY This control adjustment determines the amount of error signal that occurs before the Sens P7 motor is energized in the direction determined by the input signal This is only used f...

Страница 6: ...in end position CLOSED refer to Figure 3 LEDs are not illuminated Turn potentiometer 0 P3 slightly clockwise until LED V27 yellow lights up LED V28 green is illuminated Turn potentiometer 0 P3 slight...

Страница 7: ...To prevent exceeding the max permissible number of starts refer to Technical data sheet SG SAR or consult factory in extreme cases a time delay between 0 5s left stop and 10s right stop may be set wit...

Страница 8: ...ow lights up LED V27 yellow is illuminated Turn potentiometer max P4 clockwise until LED V27 yellow goes out Then turn potentiometer max P4 slightly counter clockwise until LED V27 yellow lights up ag...

Страница 9: ...ioner and set according to the specified nominal value E1 After setting for Split Range operation perform further readjustment as described in Calibration section Page 6 Figure 4 Positioner board A7 S...

Страница 10: ...3 4 5 0 5v 0 5v 3 ON ON 1 2 3 4 5 1 2 3 4 5 0 5v 4 20 mA ON ON 1 2 3 4 5 1 2 3 4 5 0 10v 0 5v ON ON 1 2 3 4 5 1 2 3 4 5 4 20 mA 0 5v 3 ON ON 1 2 3 4 5 1 2 3 4 5 Fail close 4 20 mA 4 20 mA ON ON 1 2 3...

Страница 11: ...diately after loss of E1 and remains in this position Fail close Actuator runs to the closed position after loss of E1 Fail open Actuator runs to the open position after loss of E1 2 Signals from inte...

Отзывы:

Похожие инструкции для Matic Series