ELECTRICAL INSTALLATION
710-02407-00G CSX
Page
3
3.1
Power Terminations
0.14 - 1.5
(26 - 16)
0.14 - 1.5
(26 - 16)
N.A.
3.5 mm
0.5 Nm max
4.4 in-lb max
N.A.
N.A.
075 ~ 1 10
10 - 35
(8 - 2)
10 - 35
(8 - 2)
Torx (T20)
3 Nm
2.2 f t-lb
7 mm
3 Nm
2.2 f t-lb
007 ~ 030
25 - 50
(4 - 1/0)
25 - 50
(4 - 1/0)
Torx (T20)
4 Nm
2.9 f t-lb
7 mm
4 Nm
2.9 f t-lb
037 ~ 055
007 ~ 1 10
N.A.
N.A.
26
(1.02)
11
(0.43)
Ø 8.5
(0.33)
14
(0.55)
6
(0.24)
mm (inch)
mm (inch)
14
(0.55)
mm (inch)
L1/1, L2/3, L3/5,T1/2, T2/4, T3/6
mm
2
(A WG)
A1, A2, A3, 01, 02, B4,
B5, 13, 14, 23, 24
mm
2
(AWG)
mm (inch)
03236.
B
3.2
Control Voltages
CSX soft starters can be supplied in either of two control voltage configurations:
CSX-xxx-xx-C1 ..... 110-240 VAC (+ 10% / - 15%) or 380-440 VAC (+ 10% / - 15%)
CSX-xxx-xx-C2 ..... 24 VAC/VDC (± 20%)
WARNING
Always apply control voltage before (or with) mains voltage.
CAUTION
With 24 VAC/VDC use contacts rated for low voltage and low current (gold flash or similar).
3.3
Control Circuits
Two-wire Three-wire
Start/stop. To reset a trip, close then open 02.
Start.
Stop. To reset a trip, close then open 02.
WARNING
Isolate the soft starter completely from the power supply before attempting any work on the
starter or motor. Control terminals may be at phase voltage potential.