7.4

 

Semiconductor Fuses 

Semiconductor fuses can be used with CSX soft starters to reduce the potential for damage to SCRs from 
transient overload currents and for Type 2 coordination. CSX soft starters have been tested to achieve Type 
2 coordination with semiconductor fuses. Suitable Bussman and Ferraz semiconductor fuses are detailed 

below. 

 

CSX Model 

SCR I

2

(A

2

S) 

Ferraz Fuse 

European/IEC Style 

(North American Style) 

Bussmann Fuse 

Square Body 

(170M) 

Bussmann Fuse 

British Style (BS88) 

007 1150 

6.6URD30xxxA0063 

(A070URD30xxx0063) 

170M-1314 63 

FE 

015 8000 

6.6URD30xxxA0125 

(A070URD30xxx0125) 

170M-1317 160 

FEE 

018 10500 

6.6URD30xxxA0160 

(A070URD30xxx0160) 

170M-1318 160 

FEE 

022 15000 

6.6URD30xxxA0160 

(A070URD30xxx0160) 

170M-1318 180 

FM 

030 18000 

6.6URD30xxxA0160 

(A070URD30xxx0160) 

170M-1319 180 

FM 

037 51200 

6.6URD30xxxA0250 

(A070URD30xxx0250) 

170M-1321 250 

FM 

045 80000 

6.6URD30xxxA0315 

(A070URD30xxx0315) 

170M-1321 250 

FM 

055 97000 

6.6URD30xxxA0315 

(A070URD30xxx0315) 

170M-1321 250 

FM 

075 168000 

6.6URD31xxxA0450 

(A070URD31xxx0450) 

170M-1322 500 

FMM 

090 245000 

6.6URD31xxxA0450 

(A070URD31xxx0450) 

170M-3022 500 

FMM 

110 320000 

6.6URD31xxxA0450 

(A070URD31xxx0450) 

170M-3022 500 

FMM 

 

xxx = Blade Type.  Contact Ferraz for options. 

 

Содержание CSX-007

Страница 1: ...nual are included solely for illustrative purposes The information contained in this manual is subject to change at any time and without prior notice In no event will responsibility or liability be accepted for direct indirect or consequential damages resulting from the use or application of this equipment WARNING ELECTRICAL SHOCK HAZARD CSX soft starters contain dangerous voltages when connected ...

Страница 2: ...75 CSX 090 202 160 240 204 214 114 5 51 6 1 CSX 110 7 95 6 30 9 45 8 03 8 43 4 50 2 0 13 45 2 2 Physical Installation CSX 007 CSX 055 Allow 100 mm 3 94 inches between soft starters CSX 075 CSX 110 Allow 200 mm 7 88 inches between soft starters CSX 007 CSX 055 Allow 50 mm 1 97 inches between the soft starter and solid surfaces CSX 075 CSX 110 Allow 200 mm 7 88 inches between the soft starter and so...

Страница 3: ...236 B 3 2 Control Voltages CSX soft starters can be supplied in either of two control voltage configurations CSX xxx xx C1 110 240 VAC 10 15 or 380 440 VAC 10 15 CSX xxx xx C2 24 VAC VDC 20 WARNING Always apply control voltage before or with mains voltage CAUTION With 24 VAC VDC use contacts rated for low voltage and low current gold flash or similar 3 3 Control Circuits Two wire Three wire Start ...

Страница 4: ...nals 23 24 can be used to signal run status This relay is normally open The relay operates when the soft start is complete the bypass relays are closed and full voltage is being applied to the motor The relay can be used to operate a contactor for power factor correction capacitors or to signal soft starter run status to an automation system 3 5 Electrical Schematics Figure 1 Soft starter installe...

Страница 5: ... take to reach full speed 1 Set the Initial Start Time to 20 seconds 2 Set the Initial Start Voltage as required for the application 3 Attach a current monitoring device to output T1 4 Start the motor under normal load conditions Record the time required for the measured current to fall to or below the motor s rated full load current t1 then stop the motor 5 Set Initial Start Time t1 NOTE The Init...

Страница 6: ...ft starter is running These trip points are not adjustable In pre start starting and stopping modes the high and low frequency limits both apply with no time delay A supply frequency trip will also occur if all three input phases are lost while the soft starter is running all three input phases fall below 120 VAC at start or while the soft starter is running the line contactor opens while running ...

Страница 7: ...Performance monitoring motor current motor temperature Trip code display 4 20 mA analog output Motor Current 6 3 Communication Interfaces CSX soft starters support network communication using the Profibus DeviceNet and Modbus RTU protocols 6 4 Pump Application Interface The Pump Application Interface expands the soft starter s input and output functionality for applications where greater control a...

Страница 8: ... IP00 Operating temperature 10 C to 60 C Storage temperature 25 C to 60 C to 70 C for less than 24 hours Humidity 5 to 95 Relative Humidity Pollution degree Pollution Degree 3 Vibration IEC 60068 Test Fc Sinusoidal 4 Hz to 13 2 Hz 1 mm displacement 13 2 Hz to 200 Hz 0 7 g EMC Emission Equipment class EMC Class A 1 Conducted radio frequency emission 0 15 MHz to 0 5 MHz 90 dB µV 0 5 MHz to 5 MHz 76 ...

Страница 9: ...ge C1 110 240 VAC 380 440 VAC C2 24 VAC VDC Mains voltage V4 200 440 VAC V6 200 575 VAC Nominal kW rating 400 VAC 30 kW AC53b 4 6 354 37 kW AC53b 4 6 594 7 3 Current Ratings AC53b 4 6 354 1000 metres AC53b 4 20 340 1000 metres 40 C 50 C 40 C 50 C CSX 007 18 A 17 A 17 A 15 A CSX 015 34 A 32 A 30 A 28 A CSX 018 42 A 40 A 36 A 33 A CSX 022 48 A 44 A 40 A 36 A CSX 030 60 A 55 A 49 A 45 A AC53b 4 6 594...

Страница 10: ...88 007 1150 6 6URD30xxxA0063 A070URD30xxx0063 170M 1314 63 FE 015 8000 6 6URD30xxxA0125 A070URD30xxx0125 170M 1317 160 FEE 018 10500 6 6URD30xxxA0160 A070URD30xxx0160 170M 1318 160 FEE 022 15000 6 6URD30xxxA0160 A070URD30xxx0160 170M 1318 180 FM 030 18000 6 6URD30xxxA0160 A070URD30xxx0160 170M 1319 180 FM 037 51200 6 6URD30xxxA0250 A070URD30xxx0250 170M 1321 250 FM 045 80000 6 6URD30xxxA0315 A070U...

Страница 11: ...NOTES 710 02407 00G CSX Page 11 ...

Страница 12: ...NOTES Page 12 CSX 710 02407 00G ...

Отзывы: