TD400P Programmable Temperature Controller  

Version 1.1 (Oct, 2017) 

 

1.

 

Overview 

This is a dual-output temperature controller with 8 programmable steps. It 
contains one temperature probe and two independent outputs. One output is 
for cooling device such as refrigerator and the other one is for heating device. 
The temperature control can be programmed to vary with different time step 
setting. Up to 8 temperature-time steps covering 33 days can be programmed. 
It can be used for applications such as beer fermentation or convert a 
refrigerator to kegerator. By using both cooling and heating devices, the 
refrigerator can be controlled at specific temperature regardless in hot summer 
or cold winter. 

This controller is a plug and play controller. No wiring is needed for the heater 
or cooler. Both the heating and cooling control modes are simple on/off control, 
similar to a mechanical thermostat but with much higher precision due to 
adjustable hysteresis band, precise sensor and digital read out. Anti-short 
function is provided for cooling to protect the compressor from being turned on 
with high pressure Freon. 

Different operation temperature ranges of the two outputs can be set 
separately. Once the cooling range is set, the controller program will 
automatically limit the heating range to prevent both heating and cooling from 
being turned on at the same time.  

A digital silicon band gap sensor is used. The advantage is being much more 
reliable in moisture environment than thermistor sensor. It can be immersed 
over extended period of time. It also has a more uniform accuracy over an 
entire specified temperature range. 

2.

 

Specifications 

Table 1. Specifications 

Temperature Control Range 

-50 ~ 105° C, -58 ~ 221° F 

Temperature Resolution 

0.1° C (between -9.9 ~ 99° C) 
1° C (between -50 ~ 10° C, 100 ~ 120° C) 
0.1° F (between -9.9 ~ 99.9° F) 
1° F (between -58 ~ 10° F, 100 ~ 248° F) 

Temperature Accuracy 

0.5 ° C or 0.9 ° F 

Temperature Control Mode 

On/Off Control. Heating and Cooling 

Temperature Control Output 

10A, 120 V or 240 VAC * 

Timer Range 

Each step: 0.1 to 99.9 Hours or 1 to 999 
Minutes 

Timer Resolution 

0.1 Hours or 1 Minute 

Max Programmable Time 

799.2 hours or 33.3 days (for total 8 steps) 

Audio Alarm 

High and low limit 

Sensor Type 

Silicon Band Gap Sensor 

Sensor Size 

0.25" OD (6.35 mm) x 1" (25mm) long 

Ambient Temperature 

-20 ~ 50° C (0 ~ 120° F) 

Dimension 

91 x 140 x 46mm 

Input Power  

85  ~ 242 VAC, 50 Hz / 60 Hz 

Sensor Cable Length 

6 ft (2 m) 

Power Cable Length 

3 ft (1 m) 

Warranty: One (1) year. 

*: Either heating or cooling device is limited to 10 Amps. The output voltage is 
same as input voltage.  When the controller is plugged into 120V AC, the 
output will be 120VAC. If the controller is connected to 240 VAC, the output will 
be 240VAC also. 
 

3.

 

Front Panel  

Up Key

Down Key

Set Key

Cooling Device 

Socket

Heating Device 
Socket

Heating Device 
Indicator

Cooling Device

Indicator

Display

Start Key

Pause/Stop Key

Mute Key

Prog. Step Key

Run indicator

Figure 1. Front Panel. 

 

Display window

: display temperature reading and parameters.  

RUN indicator

: the green LED indicator is on when the program is running.  

START key

: start executing the program.  

PAUSE/STOP key

: short press it to pause the program; long press it for 4 

seconds to stop the program (only when the program is already been paused).  

MUTE key

: silent the alarm buzzer.  

STEP key

: jump to different step; check the running step.  

SET key

: access the program settings and parameter settings. 

UP key

: increase the value. 

DOWN key

: decrease the value. 

Cooling device socket

: supply power to cooling device.  

Cooling device indicator

: green LED indicator; it is on when the cooling 

device socket is energized. 

Heating device socket

: supply power to the heating device.   

Heating device indicator

: red LED indicator lit; it is on when the heating 

device socket is energized.  
 

4.

 

Basic Operation 

Here are the basic operating procedures to use this controller. To fully 
understand the functions on this controller, please read the entire manual.   
1) Connect the temperature sensor to the sensor socket that is located on the 
top of the controller. Please check the alignment of the slot on the plug with the 
key on the socket. (See section 12 for details.) 
2) 

Plug the controller’s power cord to a wall outlet. 

 

3) Set up the program and system parameters. Please read the rest of this 
manual for details. 
4) Connect the cooling device and/or heating devices to the output sockets on 
this controller. 
5) Press START key to start running the program.     

Instruction Manual

 

 

Содержание TD400P

Страница 1: ...Minute Max Programmable Time 799 2 hours or 33 3 days for total 8 steps Audio Alarm High and low limit Sensor Type Silicon Band Gap Sensor Sensor Size 0 25 OD 6 35 mm x 1 25mm long Ambient Temperature 20 50 C 0 120 F Dimension 91 x 140 x 46mm Input Power 85 242 VAC 50 Hz 60 Hz Sensor Cable Length 6 ft 2 m Power Cable Length 3 ft 1 m Warranty One 1 year Either heating or cooling device is limited t...

Страница 2: ...erential 0 5 99 9 5 0 4 oFS Ofs Temp Offset 99 9 99 9 0 5 AS AS Anti short Cycle Delay only for cooling socket M 0 M99 0 99 min M 0 6 A M A M Power Outage Startup Modes S M C S 7 PrG PrG Program Modes on off ON 8 SFA SFA Sensor Failure Operation 0 0 0 1 1 0 0 0 9 Time time Time unit H M H 10 C F C F Temperature unit ºF ºC ºF 11 Note 1 AH deviation high alarm AL deviation low alarm Assuming measure...

Страница 3: ...ess temperature alternatively This mode is suitable for situations where the operator s attention is needed after power interruption occurs Note 8 PrG Program Mode When PrG is set to ON user can program up to 8 steps Section 7 When set it to OFF this multi step function is disabled and controller is in single step mode User can only set C 1 value without timer t 1 when disabled Please be aware tha...

Страница 4: ... part of the program by jumping to a specified program step For example the controller has run 3 minutes in its 2nd step If the user want to skip the rest of the 2nd step and the entire 4th step then the user can jump to step 4 To jump to a specified step 1 Put the controller in either Program Hold or Stop Mode 2 Press STEP key so the controller will flash J PX where J indicates this operation is ...

Страница 5: ...ble To install the sensor to the controller 1 Identify the key on the male sensor connector Figure 5 a and the notch on the female connector Figure 5 b 2 Hold the tail of the female connector align the notch and the key and push the female connector forward To remove the connector hold the spring loaded collar on the female connector and pull it back Please see Figure 6 a b c Figure 5 Install the ...

Отзывы: