background image

 

 AUBER INSTRUMENTS

    

 

 

 

 

 

 

            

WWW.AUBERINS.COM 

 

2019.01             

 

 

               P2/6 

contact  and  other  may  need  N.C.  contact  switch.  Please  see  Fig.  7  and  9  for 
examples. 
 

3.3 Control output connection 

The relay output of SWA-2441A can be used to turn on an external contactor or 
a  solenoid  valve.  This  controller  can  also  drive  a  small  heater/load  directly,  if 
this load draws less than 10A/120V. 
 

3.3.1

  Connecting  the  load  through  a  contactor:  Assuming  the  controller  is 

powered  by  120V  AC  and  the  contactor  has  a  120V  AC  coil,  jump  a  wire 
between  terminals  9  and  7.  Connect  terminal  10  to  one  lead  of  the  coil  and 
terminal 6 to the other lead of the coil. Please see Figure 6 for example.  
 

3.3.2

  Connecting  the  heater  (or  cooler)  directly  from  the  internal  relay. 

Assuming  the  controller  and  the  load  (heater  or  cooler)  are  powered  by  the 
same voltage. Jump a wire from terminal 9 to 7. Connect terminal 10 to the one 
lead of the load and terminal 6 to the other lead of the load. Please see Figure 7 
for details. 
 

3.4 For first time users without prior experience with PID controllers, the 
following notes may prevent you from making common mistakes. 

3.4.1

 Power to the relay output does not flow through terminal 6 and 7 of the 

controller.  The  controller  consumes  less  than  2  watts  of  power,  and  it  only 
provides a control signal to the  relay. Therefore, wires in the 18 to 26  gauge 
range should be used for providing power to terminals 6 and 7. Thicker wires 
may be more difficult to install. 
 

3.4.2

 The control relay output and the alarm output are dry single pole switches. 

They do not provide power by itself. External power source is needed for wiring 
the relay outputs. See examples 6 or 7 for details. 

 

3.4.3.

 The output of this controller is controlled by regulating the duration of on 

time for a fixed period of time. It is not controlled by regulating amplitude of the 
voltage  or  current.  This  is  often  referred  as  time  proportional  control.  For 
example, if the cycle rate is set for 100 seconds, a 60% output means controller 
will switch on the power for 60 seconds and off for 40 seconds (60/100 = 60%). 
Almost  all  high-power  control  systems  use  time  proportional  control  because 
amplitude proportional control is too expensive and inefficient. 
 

4. Front Panel and Operation 
 

 

Figure 2. Front panel.

 

1.

 

PV display: Indicates the sensor read out, or process value (PV). 

 

2.

 

SV display: Indicates the time when timer is used. If timer is deactivated, it 
indicates  the  set  temperature  (SV).  In  manual  control  mode,  an 

H

  is 

displayed  on  the  most  left  digit  to  indicate  number  is  for  percentage  of 
output (%). 

 

3.

 

Output indicator: It is synchronized with control output (terminal 9 and 10), 
and the power to the load. When it is on, the heater (or cooler) is powered. 

 

4.

 

AL1 indicator: It is synchronized with alarm 1 relay (AL1). When timer is on, 
it works as the timer relay output indicator.  When timer is deactivated, it 
lights when Alarm 1 condition meets. 

 

5.

 

AL2  indicator:  It  is  synchronized  with  alarm  2  relay  (AL2).  It  lights  when 
Alarm 2 condition meets. 

 

6.

 

Auto-tune indicator: It lights up when auto-tune starts. 

 

7.

 

SET key: Press and hold this key for 3 seconds will enter the temperature 
control parameter setting  mode. When the controller is in temperature,  or 
timer  parameter  setting  mode,  press  this  key  momentarily  will  lead  the 
display to the next parameter. 

 

8.

 

Automatic/Manual function key/Data shift key 

: press 

◄ 

for 3 seconds to 

enter manual tuning mode. Press 

◄ 

for 3 seconds again to exit. 

 

9.

 

Decrement key 

: Decreases numeric value of the setting value. Press for 

3 seconds to enter the timer setting mode. 

 

10.

 

Increment key 

: Increases numeric value of the setting value. Press for 3 

seconds to enter the temperature setting mode.

 

4.1 Display Modes 

 

8888

20

PV

SV

 for 3s

Power on

Figure 3. Display modes

For 

3s

For 

3s

PV

SV

SV

PV

SP

100

tE1

20

 for 3s

PV

SV

8888

H      0

PV

SV

AL1

999.9

SET for 3s

Mode 1

Mode 2

Mode 3

Mode 4

Mode 5

 

Display mode 1: Normal operation display.

  

PV is the abbreviation for Process Value. SV is the abbreviation for Set Value. 
When the power is turned on, the upper display window shows the measured 
temperature value. If the timer is used, the lower window shows set timer value. 
When  timer  starts,  it  shows  the  time  as  it  counts  up  or  down.  If  the  timer  is 
disabled (INT = 0), the lower display shows the set temperature. 

Display mode 2: Changing temperature set value (SV)

  

Press the 

key for 3 seconds, and then release it. The decimal point on the 

lower right corner will start to flash. Press the 

or 

 key to change SV until 

the desired value is displayed. If the change of SV is large, press the 

 key to 

move the flashing decimal point to the desired digit that needs to be changed. 
Then press the 

or 

key to start  changing SV from that digit. The decimal 

point will stop flashing after no key is pressed for 3 seconds. The changed SV 
will be automatically registered without pressing the SET key. 

Display mode 3: Timer parameter set up.  

Press  the 

  key  for  3  seconds  to  change  the  display  status  into  timer 

parameter setting mode. The upper display window shows the timer parameter 
symbol to be changed, the lower display shows its value. Press the 

or 

 

to change the setting. Then, press  SET to go to next parameter. If  no  key is 
pressed  for  10  seconds,  the  display  will  return  to  mode  1  automatically.  The 
change of value will take effect without the need for pressing the SET key. See 
4.14 to 4.16 for more details. 

 

Отзывы: