6. Parameter Settings 

All parameters are listed in the table below.  
 
Press and hold SET key for 3 seconds to enter the menu mode. For each 
parameter setting, use UP or DOWN key to select different programming 
values. Press SET key to confirm then exit. Please check figure 3 for details. 
For the definition of each programming value, see Table 1. 
  

Table 1. Parameter Description. 

Code 

Description 

Range 

Initial 

No

te 

Set Values 

(Short-press SET key) 

T1 

T1 

Set value for T1

 

 

1

:

10 

T2  

T2 

Set value for T2 

 

1

.

10 

2  

Parameters  

(Long-press SET key for 3 seconds) 

FUNC 

Func 

Timer function, operating 

mode 

SDL, 

DINT, 

CYCL, 

EST * 

sdl 

3 * 

T1U 

T1u 

T1 timer unit

 

S, 

M:S, 

M, 

H:M 

M

:

T2U 

T2u 

T2 timer unit

 

TDIR 

Tdir 

Timer counting direction

 

UP, DN 

DN 

OUT 

Out 

Relay output mode

 

OFDL, 

ONDL 

OFDL 

RUN 

run 

Timer triggering action

 

RST, PU 

RST 

STOP 

stop 

Relay action when STP 

key is pressed 

0, 1 

8 ** 

PAUS 

paus 

Relay action when PAU 

key is pressed 

0, 1 

  

* Please note that ESP function is a new feature added to JSL-64A. It is not available in 
JSL-64. 
** Please note that STOP parameter will only appear in the menu when FUNC = SDL 
and OUT = ONDL.

   

 

 
Details about each parameter 
 
Note 1

.

 T1 

is the set value in Single Delay (

SDL

) mode. It is also the first set 

value in in Delayed Interval Mode (

DINT

) and the Cycled Mode (

CYCL

) mode. 

 

Note 2.

 

T2

 is the second set value in Delayed Interval Mode (

DINT

) or in the 

Cycled Mode (

CYCL

). This parameter will only be displayed if the Timer Mode 

FUNC

 is set to either 

DINT

 or 

CYCL

 mode.  

 

  

Note 3: FUNC 

is the timer operating mode, it can be set to 

SDL

DINT

CYCL

or 

EST

 

SDL

 

(Single Delay)

:

 The timer counts a single period of time that is 

defined in 

T1

. The relay can either be turned on during this period of timer or it 

can be turned on at the end of this period of time, depends on the 

OUT

 setting. 

When 

OUT

 = 

OFDL

, the relay turns on at the beginning when timer starts 

counting, and turns off when the counting stops. When 

OUT

 = 

ONDL

, the relay 

stays off when timer starts counting, and the relay turns on when the timer 
reaches the set value till the RST (reset) key is pressed or when the power to 
the device is cycled. Please refer to Note 6 for details about 

OUT

 parameter.   

 
In Single Delay and On-Delay mode (i.e., 

FUNC

 = 

SDL

OUT

 = 

ONDL

), a 

special parameter 

STOP

 will appear in the parameter menu. For details 

please refer to the Note 8 below. 
 

DINT

 (Delayed Interval): The timer will count time for two periods of time, 

T1

 and 

T2

, and then stops. Relay action depends on the 

OUT

 setting. When 

OUT

 =

OFDL

, the relay turns on at the end of T1, stays on during T2 time, and 

then turns off at the end of T2 time. When 

OUT

 = 

ONDL

, the relay turns on at 

the beginning at T1 time, turns off at the end of T1 time, stays off during T2, 
and then turns on again at the end of T2 time. This is a single action process.   
 

CYCL

 (Cycle): The timer will repeat a counting cycle that consists of two 

periods of time, T1 and T2. The relay turns on/off during each cycle depending 
on the OUT setting. When 

OUT

 = 

OFDL

, the relay turns on at the end of T1, 

stays on during T2 time, and then turns off at the end of T2 time. When 

OUT

 = 

ONDL

, the relay turns on at the beginning at T1 time, turns off at the end of T1 

time, stays off during T2, and then turns on again at the end of T2 time. This 
cycle will be immediately repeated till it is stopped or reset.  
 

EST

 (Espresso Shot Timer): This is a special mode designed for counting 

the shot time (brew time) on an espresso machine. The timer display resets to 
zero and it starts counting up when the pin 9 and 10 are shorted together. The 
timer stops counting when terminal 9 and 10 are disconnected. The time unit is 
determined by the parameter 

T1U

. Pressing the RST key can clear the display. 

The relay output, STP key, and PAU key are not functional in this mode. The 
settings of parameter T2U, TDIR, OUT, RUN, STOP, and PAUS are irrelevant 
to this mode.   
 

Note 4. T1U 

and

 T2U

 define the time unit for 

T1

 and 

T2

. (Note, T2 is only 

available when 

FUNC

 = 

DINT

 or 

CYCL

). 

 

Settings  Description 

Range 

Seconds 

0.01 s ~ 99.99 s 

M:S

 

Minutes: Seconds 

1 s ~ 99 m 59 s 

M

 

Minutes 

1 m ~ 9999 m 

H:M

 

Hours: Minutes 

1 m ~ 99 h 59 m 

 
 

Note 5

TDIR

 determines the Timer Counting Direction.   

 

UP

: counting up.

 

DN

: counting down. 

 

Note 6

.

 OUT

 determines the relay output status as the timer runs. 

OFDL

 (off-delay): the relay will turn ON when timer starts counting and 

the relay will turn OFF when the timer reaches the set value. 

ONDL

 (on-delay): the relay will stay OFF when the timer starts counting 

and the relay will turn ON when the timer reaches the set value.  
 

Note 7

.

 RUN

 determines how does the timer start counting.   

PU

 (power up): the timer starts counting when the device is powered up.  

RST

 (reset): the timer starts when reset button is pressed and released. 

 

 

 

 

 

Содержание JSL-64A

Страница 1: ...d hold it for 3 second will enter the programming mode This key is disabled when timer is running 6 DOWN key STP key Reduces the value in the programming mode when the timer is running press it to stop the timer For special stop function in single delayed on mode please see note 6 on page 3 for details 7 UP key PAU key Increases the value in the programming mode when timer is running press and hol...

Страница 2: ...f the keys on the timer are described below Please also refer to Section 6 for details of parameter RUN STOP and PAUS The settings of these parameters can affect the actual functions of STP PAU and RST key Key Action SET Shot press bring up the set value select parameter save value Long press bring up the parameter menu No action while timer is running STP Stops the timer from counting time May st...

Страница 3: ... a special parameter STOP will appear in the parameter menu For details please refer to the Note 8 below DINT Delayed Interval The timer will count time for two periods of time T1 and T2 and then stops Relay action depends on the OUT setting When OUT OFDL the relay turns on at the end of T1 stays on during T2 time and then turns off at the end of T2 time When OUT ONDL the relay turns on at the beg...

Страница 4: ...U key is pressed When PAUS 0 pressing the PAU key will only pause the timer and it will NOT affect the relay output status When PAUS 1 pressing the PAU key will not only pause the timer but also change a relay output status from ON to OFF However it will not affect relay status if the relay is OFF 7 Wiring Examples 1 Signal controlled by switches Power 120 or 240V AC is sent to pin 1 and 2 The ext...

Страница 5: ...be triggered when stop key switch is released voltage from low to high Power Relay output Reset Pause Stop T1 Ta Tb Ta Tb T1 Figure 10 a Single delay and off delay FUNC SDL OUT OFDL Power Relay output Reset Pause Stop 0 T1 Ta Tb Ta Tb T1 Stop 1 Figure 10 b Single delay and on delay FUNC SDL OUT ONDL for the STOP parameter please see Note 8 on page 2 for details Power Relay output Reset Pause Stop ...

Отзывы: