29
Guides are only intended for use on Atwood
®
products by service technicians who have successfully completed
Atwood
®
training. This guide should be used in conjunction with the appropriate Instruction Manual provided with the
product and any applicable Industry Standards. This is not intended to be a complete list. Please direct questions
concerning service of Atwood
®
products to 800-825-4328 option 5 before proceeding.
CAUSE
SOLUTION
B L O W E R D O E S N O T R U N
Temperature selector out of place
--------------------
Re-set to desired position
Thermostat wires broken or disconnected
----------
Not covered under warranty.
Heat anticipator burned out
--------------------------
Dead short (not covered under warranty). Repair short and then replace
thermostat.
Faulty relay drawing more than 1 amp. Replace relay and thermostat. Covered
under warranty.
No continuity through thermostat with
contacts closed and switch on.
----------------------
Replace thermostat.
Continuity through thermostat with
contacts closed and switch on.
----------------------
• Check and reestablish power to thermostat
• Reset tripped circuit breaker.
• Correct poor ground.
• Correct any loose wires.
• Replace defective relay.
• Replace defective motor.
F U R N A C E D O E S N O T C Y C L E P R O P E R LY
Furnace cycles too quickly
----------------------------
Move anticipator to a higher amp setting to lengthen cycle. NOT covered
under warranty.
Thermostat located too close to a heat duct. Move thermostat or duct outlet.
NOT covered under warranty.
High temperature variance
----------------------------
Move anticipator to a lower amp setting to shorten cycle. NOT covered under
warranty.
Note: When the anticipator is set properly and the heating system has operated for a few hours, the furnace should
cycle 5-6 time per hour.
hydro flame Thermostat
TROUBLE SHOOTING GUIDE
Effective: 8/10/98