Instrument panel
ATTACK DPX STANDARD
The wood gasifying boiler "ATTACK DPX Standard" is controled by boiler and flue gas
thermostat.
1 – Emergency
thermostat with reset
2 - Fuse
3 - Main switch
4 - Flue gas thermostat
5 - Boiler thermostat
6 –Thermomanometer
Description:
1.
Emergency thermostat with reset - boiler protection against overheating (after reaching
temperature higher than 110°C it comes to boiler disconnection from electricity mains) after
decrease of water temperature under 85°C it is necessary to push the restart button manually
after removing cover of reset .
2.
Fuse - boiler protection against short circuit
3.
Main switch - boiler start and complete boiler stop for the case of need.
4.
Flue gas thermostat - at decrease of flue gas temperature under adjusted value is the fan
switched off
ATTENTION! While heating-up, set this thermostat to 0°C. After fuel burn-out set the flue
gas thermostat to „Operation“. When the temperature decreases under adjusted value, the
suction fan is switched off. If you wish to turn the fan on again, set the lower temperature on
the flue gas thermostat. It is necessary to test the optimum setting for operation.
5.
Boiler thermostat - serves for setting of max. temperature of water in boiler (after exceeding
of adjusted value is the fan switched off and boiler works at minimum output, after decrease of
given temperature is the fan switched on again and boiler works at maximum output).
6.
Thermomanometer - indicates outlet water temperature from the boiler and operation pressure.
Pull rod of the chimney flap - serves to open and close the heat-up flap (everytime the feeding door
is opened).
Lever for exchanger cleaning - serves for cleaning of exchanger´s tubes