23
Note
Logs of bigger dimensions is necessary to cut into halves or quarters (because of the requirement of
operation to nominal output). You can burn hard as well as soft wood. Wood must be dried!
Boiler output
depends on the moisture content of wood. Output and function of the boiler is guaranteed for
maximum moisture content of 20%.
Location of the boiler:
For the installation it is necessary to keep safe distance of its surface from flammable materials by
the degree of flammability and combustibility:
- materials B, C1 and C2
200mm
- materials C3
400mm
- materials with the degree not tested by STN 73 0853 400mm
Examples of building material devided by the degree of combustibility:
- A degree- noncombustible (bricks, blocks,ceramic linings, morter, plaster)
- B degree- very difficult to ignite (heraklith
,
lignos, boards from bazalt felt
)
- C1 degree - difficult to ignite(broadleaves- beech, oak; plywood, werzalit, hard paper)
- C2 degree - normal combustibility (coniferous species -wood, pine, spruce pulpboard, solodur)
- C3 degree - easily ignited (wood pulpboards, polyurethane, PVC, foam rubber, styrofoam)
Non-combustible board or protecting fire- screen ( on the protected subject) must exceed the boiler
dimensions at least 300mm. All the other subjects from combustible materials, which are situated
near the boiler, have to be protected by non-combustible board or fire-screen, if it is impossible to
keep the safe distance.
If the boiler is located on the floor from combustible materials, the flor must be covered with the
non-combustible, thermal insulating pad exceeding the boiler planview at least 100mm on the side
with feeding door and ash door . All the solid materials of "A" degree of combustibility can be
used for thermal insulation.
When locating the boiler in the boiler room, there must be a free space of min. 1 meter in front of
the boiler and of 0,5 m from the side walls and the rear. Above the boiler there must be a free
space of min. 1 meter. This space is necessary for basic operation, maintenance and service of the
boiler. Location of the boiler in the dwelling spaces (including halls)
is not allowed!
The cross of
2
opening for air inlet to the boiler room is recommended to be at least 200cm depending on the
boiler output.
ATTENTION!
The objects from easily combustible materials cannot be placed on the boiler or the nereby in the
distance shorter than the safe distance.
If there is a danger of fire or blow up during the work ( p.e. the work with texture materials,
sizing materials, etc.) the boiler must stand off operation.
Calorific values of the most used kinds of wood
Heat energy for 1kg
Wood
Spruce
Pine
Birch
Oak
Beech
kcal
MJ
kWh
3900
3800
3750
3600
3450
16,25
15,80
15,50
15,10
14,40
4,5
4,4
4,3
4,2
4,0
Содержание DP PROFI
Страница 1: ...W W W A T T A C K S K WOOD GASIFYING BOILER ATTACK DP STANDARD PROFI INSTRUCTIONS FOR USE ...
Страница 2: ......
Страница 18: ...17 Connection of module UM 1 Regulator Regulator Gas boiler electric boiler Alarm other devices ...
Страница 32: ...31 ...
Страница 35: ...34 ATTACK DP STANDARD 95 ...
Страница 37: ...36 ATTACK DP PROFI 95 ...
Страница 39: ......