Purificare ©2015
5
Function
Description
The function of this ultraviolet disinfection unit is to provide in excess of 99.9% reduction of all water borne pathogenic
(disease causing) bacteria.
Model ATS series have a number code designation correspondent to the maximum GPM
(gallons per minute) flow rate of the unit. I.E., PFC-8 has a maximum flow capacity of 8 GPM.
Applications: PFC Units are designed to destroy micro-organisms in water supplies. The Ultraviolet lamp peak radiation
of 254 nanometer wavelength (nm) destroys or inactivates the D.N.A. (deoxyribonucleic acid) which absorbs the
Ultraviolet radiation, preventing cellular reproduction PFC units meet minimum dosages of 30,000 microwatt second per
square centimeter.
MAXIMUM CONCENTRATION LEVELS BEFORE ULTRAVIOLET:
Turbidity.................................5 NTU
Hardness..........................................7 gpg
Color.......................................None
Iron...................................................0.3 ppm
Manganese........................0.05 ppm
pH....................................................6.5 - 9.5ppm
*Note: Pre-filtration equipment may be required if these parameters cannot be maintained. Flow rate must not exceed
The PFC series has an unique design with an ultraviolet germicidal lamp housed within a single quartz sleeve surrounded
by a stainless steel pressure chamber. The chamber is fabricated out of 304 Stainless Steel.
These units come with an ultraviolet lamp designed with four pins at one end.
The quartz sleeve is intended to be placed through the disinfection chamber and will slightly protrude through the
threaded nipple. The ultraviolet lamp is placed within this quartz sleeve. The U.V. light shines through this specially
designed hard quartz sleeve for maximum disinfection efficiency to meet the requirements for bacteria reduction in
potable water.
The inlet is located on the bottom of the chamber and the outlet can be on either side dependent upon installation. A
sight Port is provided for safe and easy view of operation. A bracket is secured to the wall and the chamber is held in
place by tightening the lock nut to both mounting bracket and chamber.
PFC © 2019 • www.aquat.com
Содержание Purificare PFC-12
Страница 2: ...Purificare 2015 2 ...
Страница 7: ...Purificare 2015 7 Installation Diagram PFC 2019 www aquat com ...
Страница 9: ...Purificare 2015 9 Sample Screen Shots PFC 2019 www aquat com ...
Страница 16: ...Purificare 2015 16 Circuit Board Layout PFC 2019 www aquat com ...
Страница 21: ...Purificare 2015 21 Notes PFC 2019 www aquat com ...
Страница 22: ...Purificare 2015 22 Notes PFC 2019 www aquat com ...
Страница 23: ...Purificare 2015 23 Notes PFC 2019 www aquat com ...
Страница 24: ...Purificare 2015 24 Warranty PFC 2019 www aquat com ...