Factory Settings :
E1
The lowest value the end user can choose as the set point.
E2
The highest value the end user can choose as the set point.
E3
The differential. With a set point of 2°C and a differential of 4°C, the unit will cool until it
reaches 2°C. At this point, the compressor will then shut off and not come back on until the
unit reaches 6°C (2 + 4). The unit will cycle on and off between these two temperatures,
maintaining an average box temperature half way between.
E4
The compressor start delay is the shortest amount of time between the compressor cycling
off and coming back on. It also will delay the compressor from starting when the unit is
plugged in.
E5
&
E6
will offset the temperatures read by the box and evaporator sensors. This setting is
rarely used.
F1
The maximum amount of time that a defrost
can
last. A defrost will last for the value set in
F1
or
until the evaporator sensor reads the value set in
F3
.
F2
The defrost interval controls how often the unit goes into defrost. A setting of six
corresponds to every six hours, or four times a day. In addition, the first defrost will start an
F2
number of hours after the unit is first plugged in.
F3
The defrost termination temperature value will bring the unit out of defrost before the full
amount of time set in
F1
has been reached if the evaporator sensor ever reaches the value
set in
F3
.
F4
The display during defrost. A setting of “00” will show the current box temperature as it rises
during a defrost, while a setting of “01” will lock in the last temperature value before the
defrost began.
F5, F6, F7, F8 & F9
are advanced settings and are advised not to be changed.
C1
The temperature display units. “00” for Celsius, “01” for Fahrenheit.
Parameter
Description
Setting
E1
Low Set Limit, Celsius, (Fahrenheit)
2°C (36F°)
E2
High Set Limit, Celsius, (Fahrenheit)
20°C (68F°)
E3
Differential, Celsius, (Fahrenheit)
4°C (7F°)
E4
Compressor Star Delay, (Minutes)
3 Min
E5
Case Temperature Offset, Celsius, (Fahrenheit)
0
°
F1
Maximum Defrost Duration, (Minutes)
20 Min
F2
Defrost Interval, (Hours)
6 Hours
F3
Defrost Termination, Celsius, (Fahrenheit)
8°C (46F°)
F4
Display During Defrost
0
C1
Temperature Units, 0
=
Celsius, (1
=
Fahrenheit)
0
Содержание A1DP-RI30
Страница 2: ...General Case Information My Model is A1DP RI30 My Case Serial number is ...
Страница 4: ...Case Dimensions ...
Страница 5: ......
Страница 6: ......
Страница 7: ......
Страница 8: ......
Страница 9: ......
Страница 10: ......
Страница 11: ......
Страница 15: ......
Страница 16: ......