background image

 

 

4. 

After  all  the  horns/strobes  are  installed  and  checked,  connect  the  power  supply  of  the  fire  alarm  control 

panel and conduct automatic login. 

5. 

After a horn/strobe logs into the fire alarm control panel, the red status indicator of the horn/strobe will blink; 

after the horn/strobe receives an operation signal, the red status indicator will remain lit and the horn/strobe 

will  give  both  horn/strobe  alarm  signals.  After  the  system  is  muted  or  reset,  the  horn/strobe  will  stop 

outputting horn/strobe alarm signals and the status indicator will restore to the monitoring status and start to 

blink again. 

VII. Precautions   

1.  Pay attention to the marking and polarities of the terminals during installation and wiring. 

2.  Do  not  make  different  products  share  the  same  address  in  a  single  alarm  circuit  or  the  system  will  fail  to  operate 

normally. 

3.  Make  sure  during  installation  that  there  are  no  objects  in  front  of  the  horn/strobe  that  block  the  light  given  by  the 

horn/strobe and/or prevent the horn/strobe from sounding.   

4.  Make the installation comply with related provisions of  the Code for Installation and Acceptance of Fire Alarm System 

(GB50166-2007). 

VIII. Maintenance and inspection 

1.  As specified in national standard Code for Installation and Acceptance of Fire Alarm System (GB50166-2007), at least 

quarterly tests should be done for each horn/strobe.   

2.  If a horn/strobe fails due to a material defect or a manufacturing process defect under the normal conditions of use in 

one year following the date of its delivery, we shall repair or replace it for free. However, the faults of the horn/strobe due 

to  artificial  damages,  improper  use  or  unauthorized  adjustment,  reconstruction  or  disassembly  are  not covered  in  the 

guarantee and we shall assume no responsibility for all the consequences thereby caused. 

3.  We may  provide  a  paid  repair  service  for  the  products  with any  faults  beyond  the  guarantee  range.  If  you  have  such 

products needing repair, please contact us. When sending such a product to us for repair, you are expected to provide 

some important information about the product, such as the phenomenon and possible cause of the product fault, so that 

we can find out the cause of the fault in the shortest time and the information may be used as a reference in our future 

product development and improvement. 

IX. Fault analysis and troubleshooting 

 

Fault phenomenon   

Possible cause   

Troubleshooting method 

Remarks 

The horn/strobe cannot 

give a horn/strobe alarm 

signal. 

The wiring is wrong. 

Inspect whether or not the wiring is correct. 

 

The  linkage  function  has 
not yet been enabled. 

Inspect  whether  or  not  the  general  linkage 
indicator is lit. 

 

The  short-circuit  block  is 
set wrong. 

Inspect  whether  or  not  the  short-circuit 
block is correctly set and whether or not its 
contact is good. 

 

The 

internal  circuit 

is 

damaged. 

Send the horn/strobe back to the factory for 
repair. 

 

 

 

 
 
 

 