Installation method F according table B.52.1.
Single-core cables, touching in free air
Clearance to wall not less than one cable diameter
Maximum allowed current in function of the ambient temperature for installation method F
Ambient temperature
Cable section
30 °C
40 °C
45 °C
50 °C
55 °C
25 mm²
< 110 A
< 96 A
< 87 A
< 78 A
< 67 A
35 mm²
< 137 A
< 119 A
< 108 A
< 97 A
< 84 A
50 mm²
< 167 A
< 145 A
< 132 A
< 119 A
< 102 A
70 mm²
< 216 A
< 188 A
< 171 A
< 153 A
< 132 A
95 mm²
< 264 A
< 230 A
< 209 A
< 187 A
< 161 A
120 mm²
< 308 A
< 268 A
< 243 A
< 219 A
< 188 A
Calculation method for IEC:
• Single supply cables (3 PE - configuration (1)):
• Add 10 % to the total current (I
tot
from the tables)
• Install the prescribed fuse on each cable
• Parallel supply cable (2 x 3 PE - configuration (2)):
• Add 10 % to the total current (I
tot
from the tables) and divide by 2
• Multiply the ampacity of the cables with 0.8 (see table A.52.17 (52-E1))
• Install fuses of half the size of the recommended maximum fuse size on each cable.
• When using 2 x 3 PE as in (3):
• Add 10 % to the total current (I
tot
from the tables) and divide by √3
• Multiply the ampacity of the cables with 0.8 (see table A.52.17 (52-E1))
• Fuse size: the recommended maximum fuse size divided by √3 on each cable.
• Size of the PE cable: use following rule of thumb:
• For supply cables up to 16 mm²: same size as supply wires
• For supply cables between 16 mm² and 35 mm²: 16 mm²
• For supply cables larger than 35 mm²: half the size of the supply wires
Always check the voltage drop over the cable (less than 5 % of the nominal voltage is
recommended)!
Example:
For SF 22 FF 400 V 50 Hz IEC, I
tot
= 52 A, ambient temperature is 40 °C,
recommended fuse: maximum 63 A.
• In case of single supply cables (3 PE - configuration (1)):
• I = 52 A + 10 % = 52 x 1.1 = 57.2 A
• The table for installation method B2 allows a maximum current of 54 A for a 16 mm²
cable. For a cable of 25 mm², the maximum allowed current is 70 A, which is sufficient.
Therefore, use a 3 x 25 mm² + 16 mm² cable.
If method C is used, 16 mm² is sufficient (maximum 66 A at 40 °C). Use a 3 x 16 + 16
mm² cable.
• Install 63 A fuses.
• In case of parallel supply cables (2 x 3 PE - configuration (2)):
• I = (52 A + 10 %)/2 = (52 x 1.1)/2 = 28.6 A
Instruction book
100
2920 7140 52
Содержание SF 15+
Страница 1: ...INSTRUCTION BOOK OIL FREE SCROLL COMPRESSORS SF 15 SF 17 SF 22 SFD 11 SFD 15 SFD 22 ...
Страница 2: ......
Страница 16: ...2 2 Flow diagram Flow diagram of SF 15 SF 17 SF 22 Instruction book 14 2920 7140 52 ...
Страница 18: ...Flow diagram of SFD 11 SFD 15 SFD 22 Instruction book 16 2920 7140 52 ...
Страница 112: ......
Страница 113: ......