User manual
2920 1456 03
19
Element Outlet
C 120
(blinks)
Prog Lim Canc
↓
F1 F2 F3
Fig. 12.2 Modify parameters menu
3. The key Lim (F2) can be used to find out the limitations for the parameter. Use the
↓
or
↑
arrow
key to change the value.
4. Press the key Prog (F1) to program the new setting or the key Canc (F3) to cancel the
modification operation.
5. The screen shown in Fig. 12.1 shows an arrow pointing to the right to call up the screen to modify
the shut-down warning value:
Element Outlet
C 94
Shdw Max
110
Back Mod
F1 F2 F3
Fig. 12.3 Modify parameters menu
6. The screen shows that the current temperature is 94 °C and that the shut-down warning setting is
110 °C. The modifying procedure is similar to the description above.
Note:
The modifying procedure for other settings is similar. For some settings, a delay can be
programmed. See section 18.