11
Orders received Current absent
Full wave 230V
Negative half
wave -115V
Positive half wave
+115V
Ref/neutral
oscilloscope
Mode achieved
COMFORT
ECO
STANDBY
STOP HEATING
LOAD SHEDDING
5/ Connecting the device
- The device must be supplied
with 230V, 50Hz.
- Mains connection must be ensu-
red using the 3-wire cable facto-
ry fitte to the device, through a
connecting box. In damp premi-
ses, such as bathrooms and kit-
chens, install the connecting box
at least 25cm from the ground.
- The installation must comply
with local national regulation. If
in
doubt,
ask
the
national
Atlantic distributor.
- Ground connection is forbidden.
Do not connect the pilot
wire (
black
) to ground.
- If power cable is damaged or too
short, to avoid any danger it must be replaced by a qualified electrician using special tools.
- If a device pilots or is piloted by a 30mA differential (
e.g. bathroom
), the pilot wire supply must be
protected on this differential.
Panel heater cable
Phase=brown
Neutral=blue
PHASE
NEUTRAL
Electricity
grid
Three possible cases
Pilot wire=Black
1st case: only one heater
2nd case: Slave heater
3rd case: Master heater
The pilot wire end is insulated
and not further connected
To the appliance with cassette or
programming unit.
To pilot wire of an electronically
controlled appliance
Chart indicating the orders the device can receive over its pilot wire
(
to be measured between the pilot wire and the neutral
).
6/ Lock the device on the hook-on bracket
S
1
S2
CLICK